(in hex)
FUNCTION SETTING VALUE
125h n037 Multi-function Input Selection 2-24 When n036 is set to ‘1’; ‘—‘ will be 2
(Terminal S3) same as n036 displayed & no value may be
entered.
126h n038 Multi-function Input Selection 2-24 4
(Terminal S4) same as n036 (2; if 3-wire)*
127h n039 Multi-function Input Selection 2-24 9
(Terminal S5) same asn036 (4; if 3-wire)*
128h n040 Multi-function Input Selection 2-26 When n040 is set to ‘29’; n039
(Terminal S6) same as n036 setting is prohibited 10
(9; if 3-wire)*
129h n041 Multi-function Output 0 Fault
(Terminals MA-MB-MC) 1 During Running
(settings 0-17) 2 Speed Agree
3 Desired Speed Agree 0
4 Frequency Detection 1
5 Frequency Detection 2
6 Overtorque Detection (N.O.)
7 Overtorque Detection (N.C.)
8 During Baseblock
12Ah n042 Multi-function Output 9 Operation Mode
(Terminals M1-M2) 10 Ready
(settings 0-17) 11 Timer Function
12 During Auto Re-start 1
13 OL pre-alarm (80% of OL1 or OL2)
14 Frequency Reference Loss