(in hex)
FUNCTION SETTING VALUE
17 0H1 Alarm (only if n035 set to ‘3’)
12Bh n043 Auto Analog Input Selection 0 FV – Master; FI –Auxiliary
Auto/ Manual switch enable - Yes
0
1 FV – Auxiliary; FI – Master
Auto/ Manual switch enable - Yes
2 FV – Fault Reset; FI – Master
Auto/ Manual switch enable - No
12Ch n044 Manual Analog Input Selection
(Terminal FI)
0 0-10V input
(jumper J1 must be cut on control
PCB)
1
1 4-20mA input
12Dh n045 Frequency Reference Retention 0 Not Retained 0
(for Up/Down; Sample/Hold) 1 Retained in Freq. Reference 1 (n024)
12Eh n046 Frequency Reference 0 No Detection 0
Loss Detection 1 Continue to run at value set in (n047)
12Fh n047 Freq. Ref. Level at loss of Freq.
Detection
0-100% 80
130h n048 Freq. Reference Gain (Term. FV) 0 to 200% 100%
131h n049 Freq. Reference Bias (Term. FV) -100% to +100% 0
132h n050 Freq. Reference Gain (Term. FI) 0 to 200% 100%
133h n051 Freq. Reference Bias (Term. FI) -100% to +100% 0
134h n052 Multi-function Analog Output 0 Output Frequency (Hz)
(Terminals AM & AC) 1 Output Current (A) 0
2 Output Power (kW)
3 DC Bus Voltage (V DC)
135h n053 Analog Monitor Gain 0.01 to 2.00 1.00
136h n054 Carrier Frequency 1 to 6 x 2.5 kHz (1)