88
Table A−5 Constants List (Cont’d)
Constant
No.
Name
Initial
Setting
User
Setting
Constant
No.
Name
Initial
Setting
User
Setting
L1-01 Motor protection selection 1 o1-01 Monitor selection 6
L1-02 Motor protection time 60.0 o1-02 Monitor selection after power up 1
L2-01 Momentary power loss detection 0 o1-03
Units of speed reference setting and
monitor
1
L2-02 Momentary power loss ridethru time
*1
o2-01 LOCAL/REMOTEkeyenable/disable 1
L2-03
Deceleration time at momentary pow-
er loss
30.0 o2-02
STOPkey during control circuit termi-
nal operation
0
L2-05 Undervoltage detection level 190
*2
o2-04 kVA selection
*1 *5
L3-01
Overvoltage prevention function
selection
*3
1 o2-05
Speed reference setting method selec-
tion
0
L4-01 Speed detection level 0.0 o2-06
Operation selection when digital opera-
tor is disconnected
0
L4-02 Speed detection width 2.0 o2-07 Cumulative operation time setting
L4-03 Speed detection level (+/-) 0.0 o2-08 Cumulative operation time selection 0
L4-04 Speed detection width (+/-) 2.0 T1-02 Tuning mode 0
L4-05
Operation when speed reference is
missing
0 T1-03 Tuning item selection 1
L5-01 Number of auto restart attempts 0
L5-02 Auto restart operation selection 0
L6-01 Torque detection selection 1 0
L6-02 Torque detection level 1 150
L6-03 Torque detection time 1 0.1
L6-04 Torque detection selection 2 0
L6-05 Torque detection level 2 150
L6-06 Torque detection time 2 0.1
L7-01 Forward torque limit 160
L7-02 Reverse torque limit 160
L7-03 Forward regenerative torque limit 160
L7-04 Reverse regenerative torque limit 160
L8-01
Protect selection for internal DB resis-
tor
*4
0
L8-02 Inverter overheat pre-alarm level 95
L8-03
Operation selectionafterinverterover-
heat pre-alarm
3
L8-05 Input open-phase protection selection 0
L8-07
Output open-phase protection selec-
tion
0
L8-10 Ground fault protection selection 1
L9-01 Step-out protection selection 1
L9-02
Output current unbalance protection
selection
*6
1
*1 Setting range and initial setting differ depending on inverter capacity.
*2 Set value for 200V class. For 400V class, the value is twice as that of 200V class.
*3 When using a braking resistor unit, set L3-01 to “0.”
*4 When using a mounting-type braking resistor unit (model ERF), set L8-01 to “1.”
*5 Not initialized.
*6 The display is applicable for software No. 1033 or later (FLASH side). To check which
version is being used, refer to U1-14.