VAN-V07007E [J7J1000] Replacement Instructions
12/16
J7 J1000
Drive
Function/
Parameter
Parameter
No.
Initial Value
Parameter
No.
Initial Value
Comments
Te rm i n al MA, MB, M C
function selection
n40 1 H2-01 E
J7 J1000
n400 H2-01E
n401 H2-010
n402 H2-012
n403 H2-011
n404 H2-015
n405 H2-014
n406 H2-01B
n407 H2-0117
n4010 H2-0110
n4011 H2-018
n4012 H2-013C
n4013 H2-016
n4014 H2-011E
n4015 H2-017
n4016 H2-011A
n4017 H2-013D
n4018
F (through mode)
Analog input FR gain
n41 100% H3-03 100.0 %
Analog input FR bias
n42 0% H3-04 0.0 %
Analog input filter time
constant
n43 0.10 s H3-13 0.03 s
Analog output AM
function selection
n44 0 H4-01 102
J7 J1000
n440 H4-01102
n441 H4-01103
Analog output AM gain
n45 1.00 H4-02 100.0%
Set H4-02 = n45 * 100
Carrier frequency
selection
C6-02
o2-04
dep.
Carrier frequency
upper limit
C6-03 C6-02 dep.
Carrier frequency
lower limit
C6-04 C6-02 dep.
Carrier frequency
proportional gain
n46
4
(depending
on drive
size)
C6-05 0
J7 J1000
n461 C6-021 (2kHz)
n462 C6-022 (5kHz)
n463 C6-023 (8kHz)
n464 C6-024 (10kHz)
n467
C6-03 = 2.5
C6-04 = 1.0
C6-05 = 12
n468
C6-03 = 2.5
C6-04 = 1.0
C6-05 = 24
n469
C6-03 = 2.5
C6-04 = 1.0
C6-05 = 36
Momentary power loss
detection selection
n47 0 L2-01 0
J7 J1000
n470 L2-010
n471 L2-011
n472 L2-012
Automatic fault reset
attempts
n48 0 L5-01 0
Jump frequency 1
n49 0.0Hz d3-01 0.0Hz
Jump frequency 2
n50 0.0Hz d3-02 0.0Hz
Jump frequency
bandwidth
n51 0.0 Hz d3-04 1.0 Hz