YASKAWA VS MINI J7 - J7 and J1000 Differences in Parameter Settings

YASKAWA VS MINI J7
16 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
J7 J1000
Drive
Function/
Parameter
Parameter
No.
Initial Value
Parameter
No.
Initial Value
Comments
Memobus slave
address
n70 0 H5-01 1F
J7: set as decimal value
J1000: set as hexadecimal value
Memobus
communication Speed
selection
n71 2 H5-02 3
J7 J1000
n710 H5-021
n711 H5-022
n712 H5-023
n713 H5-024
Memobus parity
selection
n72 0 H5-03 0
J7 J1000
n720 H5-031
n721 H5-032
n722 H5-030
Transmission wait time
n73 10ms H5-06 10 ms
RTS flow control on/off
n74 0 H5-07 1
J7 J1000
n740 H5-071
n741 H5-070
Low speed carrier
frequency reduction
n75 0 L8-38
depends on
drive
capacity
J7 J1000
n750 L8-380
n751 L8-381
COPY function
selection
n76 rdy o3-01 0
Possible with copy unit or remote
operator.
READ prohibit
selection
n77 0 o3-02 0
Fault History
n78 - U2-01/02 -
In the J1000 the last current fault and the
last fault can be seen in parameter U2-01
and U2-02
Software Version
n79 - U1-25/26 -
6.2 J7 and J1000 Differences in Parameter Settings
- Maximum carrier frequency
J7: n46, max. 10 kHz
J1000: C6-02, max. 15 kHz
- S-Curve setting
J7: fixed settings
J1000: set in seconds
- Stall Prevention Level
The stall prevention level during acceleration and constant speed run depends on the duty
mode setting.
J7: The maximum setting of n56/57 is 200%
J1000: Heavy Duty, The maximum setting of L3-02 and L3-06 is 150%
Normal Duty, The maximum setting of L3-02 and L3-06 is 120%
VAN-V07007E [J7J1000] Replacement Instructions
14/16