6 Parameter Settings
6.1 J7 to J1000 Parameter Correspondence for Drive Replacement
・Before setting up other parameters, make sure that C6-01 is set to “0” (Heavy Duty). Refer to the
Technical manual for details on the Normal and Heavy Duty selection.
・The given voltage values are valid for 200 V units. For 400 V units the values have to be doubled.
VAN-V07007E [J7→J1000] Replacement Instructions
9/16
J7 J1000
Drive
Function/
Parameter
Parameter
No.
Initial Value
Parameter
No.
Initial Value
Comments
Parameter access
level
A1-01 2
Initialization
A1-03 0
Run Command in
Programming Mode
b1-08 0
Fault history U2
initialization
n01 1
o4-11 0
J7 J1000
n01→0 A1-01→0
n01→1 A1-01→2
n01→5 A1-01→2
b1-08→1
n01→6 o4-11→1
n01→8 A1-03→2220
n01→9 A1-03→3330
RUN command source
selection
n02 0 b1-02 1
J7 J1000
n02→0 b1-02→0
n02→1
b1-02→1
n02→2 b1-02→2
Frequency reference
source selection
n03 0 b1-01 1
J7 J1000
n03→0
b1-01→3 (AI-V3/J
option required)
n03→1 b1-01→0
n03→2 b1-01→1 and H3-01→0
n03→3 b1-01→1 and H3-01→2
n03→4 b1-01→1 and H3-01→3
n03→6
b1-01→2 (SI-485/J)
option required)
When using A1 as frequency reference
input, make sure to set DIP switch S1
properly (voltage or current input).
Stop method selection
n04 0 b1-03 0
J7 J1000
n04→0 b1-03→0
n04→1 b1-03→1
Reverse run prohibit
selection
n05 0 b1-04 0
J7 J1000
n05→0 b1-04→0
n05→1 b1-04→1
Digital Operator STOP
key function
n06 0 o2-02 1
J7 J1000
n06→0 o2-02→1
n06→1 o2-02→0
Frequency reference in
local mode
n07 0 - -
- (no operator panel potentiometer)
Frequency reference
from operator ENTER
key selection
n08 0 o2-05 0
J7 J1000
n08→0 o2-05→0
n08→1 o2-05→1
Max. output frequency
n09 60.0 Hz E1-04 60.0 Hz
Max. output voltage
n10 200 V * E1-05 200 V *
* Values for a 400 V class drive are double.
Base frequency
n11 60.0Hz E1-06 60.0 Hz
Mid. output frequency
n12 1.5Hz E1-07 3.0 Hz
Mid. output voltage
n13 12 V * E1-08 16.0 V *
* Values for a 400 V class drive are double.