6 Parameter Settings
6.1 J7 to J1000 Parameter Correspondence for Drive Replacement
・Before setting up other parameters, make sure that C6-01 is set to “0” (Heavy Duty). Refer to the
Technical manual for details on the Normal and Heavy Duty selection.
・The given voltage values are valid for 200 V units. For 400 V units the values have to be doubled.
VAN-V07007E [J7J1000] Replacement Instructions
9/16
J7 J1000
Drive
Function/
Parameter
Parameter
No.
Initial Value
Parameter
No.
Initial Value
Comments
Parameter access
level
A1-01 2
Initialization
A1-03 0
Run Command in
Programming Mode
b1-08 0
Fault history U2
initialization
n01 1
o4-11 0
J7 J1000
n010 A1-010
n011 A1-012
n015 A1-012
b1-081
n016 o4-111
n018 A1-032220
n019 A1-033330
RUN command source
selection
n02 0 b1-02 1
J7 J1000
n020 b1-020
n021
b1-021
n022 b1-022
Frequency reference
source selection
n03 0 b1-01 1
J7 J1000
n030
b1-013 (AI-V3/J
option required)
n031 b1-010
n032 b1-011 and H3-010
n033 b1-011 and H3-012
n034 b1-011 and H3-013
n036
b1-012 (SI-485/J)
option required)
When using A1 as frequency reference
input, make sure to set DIP switch S1
properly (voltage or current input).
Stop method selection
n04 0 b1-03 0
J7 J1000
n040 b1-030
n041 b1-031
Reverse run prohibit
selection
n05 0 b1-04 0
J7 J1000
n050 b1-040
n051 b1-041
Digital Operator STOP
key function
n06 0 o2-02 1
J7 J1000
n060 o2-021
n061 o2-020
Frequency reference in
local mode
n07 0 - -
- (no operator panel potentiometer)
Frequency reference
from operator ENTER
key selection
n08 0 o2-05 0
J7 J1000
n080 o2-050
n081 o2-051
Max. output frequency
n09 60.0 Hz E1-04 60.0 Hz
Max. output voltage
n10 200 V * E1-05 200 V *
* Values for a 400 V class drive are double.
Base frequency
n11 60.0Hz E1-06 60.0 Hz
Mid. output frequency
n12 1.5Hz E1-07 3.0 Hz
Mid. output voltage
n13 12 V * E1-08 16.0 V *
* Values for a 400 V class drive are double.