BHZ Electric Heat Minimum Supply Air
Model
(Tons)
Voltage
Minimum Supply Air (CFM)
Heater kW
5.0 7.5 10.0 15.0 20.0 25.0
BHZ024
(2.0)
208/230-1-60 630 630 800 - - -
BHZ030
(2.5)
208/230-1-60 630 630 800 800 - -
208/230-3-60 630 630 800 800 - -
460-3-60 630 630 800 800 - -
BHZ036
(3.0)
208/230-1-60 1070 1070 1070 1070 - -
208/230-3-60 1070 1070 1070 1070 - -
460-3-60 1070 1070 1070 1070 - -
BHZ042
(3.5)
208/230-1-60 1225 1225 1225 1225 - -
208/230-3-60 1225 1225 1225 1225 - -
460-3-60 1225 1225 1225 1225 - -
BHZ048
(4.0)
208/230-1-60 - - 1200 1430 1430 1430
208/230-3-60 - - 1200 1430 1430 1430
460-3-60 - - 1200 1430 1430 1430
BHZ060
(5.0)
208/230-1-60 - - 1615 1615 1955 1955
208/230-3-60 - - 1615 1615 1955 1955
460-3-60 - - 1615 1615 1955 1955
BHQ Electric Heat Minimum Supply Air
Model
(Tons)
Voltage
Minimum Supply Air (CFM)
Heater kW
3.8/5.0 5.6/7.5 7.5/10.0 11.3/15.0 15.0/20.0 18.8/25.0
BHQ024
(2.0)
208/230-1-60 720 720 720 - - -
BHQ030
(2.5)
208/230-1-60 1000 1000 1000 1000 - -
208/230-3-60 1000 1000 1000 1000 - -
460-3-60 1000 1000 1000 1000 - -
BHQ036
(3.0)
208/230-1-60 1080 1080 1080 1080 - -
208/230-3-60 1080 1080 1080 1080 - -
460-3-60 1080 1080 1080 1080 - -
BHQ042
(3.5)
208/230-1-60 - - 1400 1400 - -
BHQ048
(4.0)
208/230-1-60 - - 1440 1440 1440 1440
208/230-3-60 - - 1440 1440 1440 1440
460-3-60 - - 1440 1440 1440 1440
BHQ060
(5.0)
208/230-1-60 - - 1900 1900 1900 1900
208/230-3-60 - - 1900 1900 1900 1900
460-3-60 - - 1900 1900 1900 1900
BHX Electric Heat Minimum Supply Air
Model
(Tons)
Voltage
Minimum Supply Air (CFM)
Heater kW
5.0 7.5 10.0 15.0 20.0 25.0
BHX024
(2.0)
208/230-1-60 630 630 800 - - -
BHX036
(3.0)
208/230-1-60 1070 1070 1070 1070 - -
208/230-3-60 1070 1070 1070 1070 - -
460-3-60 1070 1070 1070 1070 - -
BHX048
(4.0)
208/230-1-60 - - 1200 1430 1430 1430
208/230-3-60 - - 1200 1430 1430 1430
460-3-60 - - 1200 1430 1430 1430
BHX060
(5.0)
208/230-1-60 - - 1615 1615 1955 1955
208/230-3-60 - - 1615 1615 1955 1955
460-3-60 - - 1615 1615 1955 1955