718419-YTG-D-0613
56 Johnson Controls Unitary Products
Additional Static Resistance
Model
(Tons)
CFM Wet Indoor Coil Economizer
1
1. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the
return air duct is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
Filter/Frame Kit Electric Heat
BHZ/BHQ/BHX
024
(2.0)
500 0.01 0.00 0.01 0.02
600 0.01 0.00 0.02 0.03
700 0.01 0.00 0.02 0.03
800 0.01 0.01 0.02 0.03
900 0.01 0.01 0.02 0.04
1000 0.02 0.01 0.02 0.04
1100 0.03 0.01 0.03 0.05
1200 0.04 0.02 0.03 0.06
BHZ/BHQ
030
(2.5)
700 0.01 0.00 0.02 0.03
800 0.01 0.01 0.02 0.03
900 0.01 0.01 0.02 0.04
1000 0.02 0.01 0.02 0.04
1100 0.03 0.01 0.03 0.05
1200 0.04 0.02 0.03 0.06
1300 0.07 0.03 0.17 -
BHZ/BHQ/BHX
036
(3.0)
700 0.01 0.00 0.02 0.03
800 0.01 0.01 0.02 0.03
900 0.01 0.01 0.02 0.04
1000 0.02 0.01 0.02 0.04
1100 0.03 0.01 0.03 0.05
1200 0.04 0.02 0.03 0.06
1300 0.04 0.03 0.03 0.07
1400 0.04 0.04 0.03 0.08
BHZ/BHQ
042
(3.5)
1100 0.03 0.01 0.03 0.05
1200 0.04 0.02 0.03 0.06
1300 0.04 0.03 0.03 0.07
1400 0.04 0.04 0.03 0.08
1500 0.04 0.05 0.04 0.09
1600 0.04 0.06 0.05 0.10
1700 0.05 0.07 0.05 0.11
1800 0.05 0.07 0.06 0.11
1900 0.06 0.08 0.06 0.11
2000 0.07 0.08 0.07 0.12
BHZ/BHQ/BHX
048
(4.0)
1100 0.03 0.01 0.03 0.05
1200 0.04 0.02 0.03 0.06
1300 0.04 0.03 0.03 0.07
1400 0.04 0.04 0.03 0.08
1500 0.04 0.05 0.04 0.09
1600 0.04 0.06 0.05 0.10
1700 0.05 0.07 0.05 0.11
1800 0.05 0.07 0.06 0.11
1900 0.06 0.08 0.06 0.11
2000 0.07 0.08 0.07 0.12
BHZ/BHQ/BHX
060
(5.0)
1100 0.03 0.01 0.03 0.05
1200 0.04 0.02 0.03 0.06
1300 0.04 0.03 0.03 0.07
1400 0.04 0.04 0.03 0.08
1500 0.04 0.05 0.04 0.09
1600 0.04 0.06 0.05 0.10
1700 0.05 0.07 0.05 0.11
1800 0.05 0.07 0.06 0.11
1900 0.06 0.08 0.06 0.11
2000 0.07 0.08 0.07 0.12