718419-YTG-D-0613
Johnson Controls Unitary Products 61
BHZ060
(5.0)
208/230-1-60 26.2 150 41 2.3 7.6
None - - - 42.7 60
2NP04501006 7.5/10 2 36.1/41.7 87.8/94.7 100/110
2NP04501506 11.3/15 2 54.2/62.5 110.4/120.8 125/125
2NH04502006 15/20 2 72.2/83.3 132.9/146.8 150/150
2NP04502506 18.8/25 2 90.3/104.2 155.5/172.9 175/175
2NE04501006 7.5 / 10 2 36.1 / 41.7 45.1 / 52.1 50 / 60
2NE04501506 11.3 / 15 2 54.2 / 62.5 67.7 / 78.1 70 / 80
2NE04502006 15 / 20 2 72.2 / 83.3 90.3 / 104.2 100 / 110
2NE04502506 18.8 / 25 1 90.3 / 104.2 112.8 / 130.2 125 / 150
208/230-3-60 17.9 120 28 2.3 7.6
None - - - 32.3 40
2NH04501025 7.5/10 1 20.8/24.1 58.3/62.3 70/70
2NH04501525 11.3/15 1 31.3/36.1 71.4/77.4 80/80
2NH04502025 15/20 2 41.7/48.1 84.4/92.4 90/100
2NH04502525 18.8/25 2 52.1/60.1 97.4/107.5 100/110
460-3-60 9.6 70 15 1.3 7.6
None - - - 17.1 25
2NP04501046 10 1 12 32.1 35
2NH04501546 15 1 18 39.7 40
2NH04502046 20 2 24.1 47.2 50
2NP04502546 25 2 30.1 54.7 60
1. Minimum Circuit Ampacity.
2. Maximum Over Current Protection per standard UL 1995.
3. Fuse or HACR circuit breaker size installed at factory or field installed.
BHZ024-060 Heat Pump With/Without Electric Heat (Continued)
Model
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Electric Heat Option
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC FLA FLA Model kW Stages Amps