FORM 100.50-EG1
25
YORK INTERNATIONAL
TABLE 10 – SUPPLY AND EXHAUST FAN MOTOR (ODP OR TEFC)
TABLE 11 – CONDENSER FAN MOTORS / EACH
NOMINAL VOLTAGE
MOTOR 208V 230V 460V 575V
HP FLA FLA FLA FLA
5.0 14.0 13.4 6.7 5.3
7.5 22.2 21.6 10.8 8.2
10.0 28.5 28.4 14.2 11.4
15.0 44.8 39.0 19.5 16.0
20.0 61.0 50.0 25.0 20.0
25.0 74.0 60.0 30.0 24.2
30.0 87.0 76.0 38.0 30.3
40.0 113.0 95.6 47.8 38.0
High Efficiency
NOMINAL VOLTAGE
MOTOR 208V 230V 460V 575V
HP FLA FLA FLA FLA
5.0 14.9 13.6 6.8 5.5
7.5 22.5 20.0 10.0 7.9
10.0 29.2 25.8 12.9 10.3
15.0 41.5 36.0 18.0 14.5
20.0 55.0 48.0 24.0 19.3
25.0 71.0 61.0 30.5 24.5
30.0 85.5 74.0 37.0 30.0
40.0 109.0 96.0 48.0 38.0
Premium Efficiency
NOMINAL VOLTAGE
NOMINAL 208V 230V 460V 575V
TONS FLA FLA FLA FLA
50 7.5 6.8 3.4 2.7
55 7.5 6.8 3.4 2.7
60 7.5 6.8 3.4 2.7
65 7.5 6.8 3.4 2.7
TABLE 12 – CONTROLS AND CONVENIENCE
OUTLET
NOMINAL VOLTAGE
DESCRIPTION
208V 230V 460V 575V
AMPS AMPS AMPS AMPS
Control Transformer 3.6 3.3 1.6 3.3
Convenience Outlet 9.6 8.7 4.3 3.5