YORK INTERNATIONAL
150
FORM 160.54-M1(503)
System Calibration
FLASH MEMORY CARD VERSION C.MLM.01.07.XXX AND C.MLM.01.07A.XXX
Chiller Style/Compressor
Proxmity
Sense
Oil
Heater
Output*
Level
Control
Period
Default
Flow
Switch
“Oil-Variable Speed Pump
Pressure Setpoint
Not Achieved” Threshold*
“Style CDE/GHJ Compr” Probe TB1-34 3.5 sec
Digital
(Paddle Type)
35 PSID
“Style E/P Compr”
Limit
Switch
TB1-64 10.0 sec
Digital
(Paddle Type)
25 PSID
“Style F/GH Compr”
Limit
Switch
TB1-64 3.5 sec
Analog
(thermal type)
35 PSID
“Style F/J Compr” Probe TB1-64 3.5 sec
Analog
(thermal type)
35 PSID
“Style F/P Compr”
Limit
Switch
TB1-64 10.0 sec
Analog
(thermal type)
25 PSID
* Not applicable to Style C and earlier chillers.
FLASH MEMORY CARD VERSION C.MLM.01.08.XXX
Chiller Style/Compressor
Proxmity
Sense
Oil
Heater
Output*
Level
Control
Period
Default
Flow
Switch
“Oil-Variable Speed Pump
Pressure Setpoint
Not Achieved” Threshold*
“Style CDE/GHJ Compr” Probe TB1-34 3.5 sec
Digital
(Paddle Type)
35 PSID
“Style E/P Compr”
Limit
Switch
TB1-64 10.0 sec
Digital
(Paddle Type)
25 PSID
“Style F/GH Compr”
Limit
Switch
TB1-64 3.5 sec
Programmable
(Analog or Digital)
35 PSID
“Style F/J Compr” Probe TB1-64 3.5 sec
Programmable
(Analog or Digital)
35 PSID
“Style F/P Compr”
Limit
Switch
TB1-64 10.0 sec
Programmable
(Analog or Digital)
25 PSID
* Not applicable to Style C and earlier chillers