24
YORK INTERNATIONAL
25
YORK INTERNATIONAL
FORM 201.19-EG4
LCWT
AIR TEMPERATURE ON CONDENSER (°F)
(°F)
100 105 110 115 120 125
TONS kW EER TONS kW EER TONS kW EER TONS kW EER TONS kW EER TONS kW EER
MODEL YCAS0288EB
40.0 245.0 324.3 8.2 236.0 346.3 7.5 227.5 369.4 6.8 214.6 383.0 6.2 178.9 354.3 5.5 131.5 312.3 4.6
42.0 253.6 325.8 8.5 244.4 347.7 7.7 235.8 370.6 7.0 220.8 380.7 6.4 181.6 347.9 5.7 133.4 307.9 4.7
44.0 262.2 327.3 8.7 252.9 349.1 7.9 244.1 371.9 7.2 227.1 378.5 6.6 184.1 341.7 5.9 135.3 303.7 4.8
45.0 266.6 328.1 8.8 257.2 349.6 8.1 248.3 372.6 7.3 230.2 377.5 6.7 185.3 338.7 6.0 136.2 301.6 4.9
46.0 271.0 328.8 9.0 261.6 350.3 8.2 252.5 373.2 7.4 233.4 376.4 6.8 186.5 335.8 6.1 137.1 299.6 4.9
48.0 279.8 330.4 9.2 270.3 351.7 8.4 261.1 374.5 7.7 237.5 370.8 7.0 188.8 330.1 6.2 138.9 295.6 5.1
50.0 288.9 331.8 9.5 279.0 353.4 8.7 268.1 372.5 7.9 240.0 362.8 7.3 191.0 324.6 6.4 140.5 291.8 5.2
52.0 298.0 333.3 9.7 288.0 354.8 8.9 274.5 370.1 8.2 243.2 356.5 7.5 193.1 319.4 6.6 142.1 288.1 5.3
55.0 311.8 335.6 10.1 301.5 357.1 9.3 284.6 367.0 8.5 247.0 346.4 7.8 196.1 311.9 6.8 144.4 282.9 5.5
MODEL YCAS0308EB
40.0 262.9 331.4 8.5 253.3 353.6 7.7 244.2 377.4 7.0 235.4 402.7 6.4 214.1 404.5 5.8 160.8 351.3 4.9
42.0 272.1 332.8 8.8 262.3 355.1 8.0 253.0 378.4 7.3 244.1 403.5 6.6 218.6 398.2 6.0 163.2 345.7 5.1
44.0 281.4 334.1 9.0 271.4 356.4 8.2 261.9 379.7 7.5 252.9 404.4 6.8 221.8 390.4 6.2 165.6 340.4 5.2
45.0 286.1 334.8 9.2 276.0 356.9 8.4 266.4 380.4 7.6 257.2 405.3 6.9 223.3 386.6 6.3 167.2 338.1 5.3
46.0 290.9 335.4 9.3 280.7 357.5 8.5 270.9 381.0 7.7 261.7 405.7 7.1 224.8 382.8 6.4 168.3 335.6 5.4
48.0 300.5 336.7 9.6 290.1 358.7 8.7 280.1 382.2 8.0 269.5 404.6 7.3 227.5 375.4 6.6 170.5 330.6 5.5
50.0 310.2 337.9 9.9 299.6 359.9 9.0 289.4 383.4 8.2 276.8 402.7 7.5 229.6 367.8 6.8 172.6 325.8 5.7
52.0 320.1 339.1 10.2 309.2 361.2 9.3 298.8 384.6 8.5 284.3 401.4 7.7 232.1 361.2 7.0 174.6 321.2 5.8
55.0 335.0 341.0 10.6 323.8 363.1 9.7 313.2 386.3 8.8 293.5 396.1 8.1 235.8 351.7 7.2 177.4 314.6 6.0
MODEL YCAS0328EB
40.0 279.4 342.5 8.7 269.2 365.5 7.9 259.5 390.0 7.2 250.1 416.3 6.5 235.8 433.2 5.9 188.3 391.1 5.2
42.0 289.2 343.8 8.9 278.7 366.9 8.1 268.9 391.1 7.4 259.4 416.9 6.7 242.5 429.1 6.1 191.3 384.6 5.3
44.0 299.2 344.9 9.2 288.5 368.1 8.4 278.4 392.2 7.6 268.7 417.9 7.0 247.8 423.6 6.3 194.4 378.3 5.5
45.0 304.2 345.5 9.4 293.4 368.5 8.5 283.1 392.9 7.8 273.3 418.7 7.1 250.5 420.8 6.5 196.3 375.6 5.6
46.0 309.3 346.1 9.5 298.4 369.1 8.7 288.1 393.1 7.9 278.1 419.1 7.2 253.2 418.1 6.6 197.7 372.5 5.7
48.0 319.6 347.2 9.8 308.5 370.1 8.9 297.8 394.4 8.1 287.7 419.9 7.4 258.4 412.7 6.8 200.4 366.6 5.8
50.0 330.0 348.3 10.1 318.6 371.2 9.2 307.7 395.5 8.4 297.5 420.8 7.7 262.9 407.1 7.0 202.5 360.4 6.0
52.0 340.4 349.4 10.4 328.9 372.3 9.5 317.7 396.6 8.6 307.3 421.8 7.9 268.0 402.3 7.2 204.9 354.8 6.2
55.0 356.4 351.1 10.8 344.5 374.0 9.9 333.1 398.0 9.0 320.1 419.8 8.3 273.8 392.9 7.5 208.3 346.9 6.4
NOTES:
1. kW = Compressor Input Power
2. EER = Chiller EER (includes power from compressors, fans, and control panels 0.8 kW)
3. LCWT = Leaving Chilled Water Temperature
4. Ratings based on 2.4 GPM cooler water per ton
5. Rated in accordance with ARI Standard 550/590-98