Ratings – R-407C Optimized (SI Units)
LCWT
AIR TEMPERATURE – CONDENSER (°C)
(°C)
25 30 35 40 45 50
kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi
MODEL YCAS0098EB
5.0 329.5 74.4 3.9 310.8 83.7 3.3 291.2 94.4 2.8 272.3 106.5 2.3 254.4 120.0 2.0 233.0 131.8 1.6
6.0 339.1 74.2 4.0 320.6 83.5 3.4 300.6 94.1 2.9 281.4 106.1 2.4 263.3 119.4 2.0 236.8 128.8 1.7
7.0 348.7 74.1 4.1 330.5 83.3 3.5 310.1 93.9 3.0 290.5 105.9 2.5 272.1 119.0 2.1 242.7 126.8 1.8
8.0 358.0 73.9 4.2 340.4 83.1 3.6 319.6 93.7 3.1 300.0 105.5 2.6 281.1 118.6 2.2 246.6 124.3 1.8
9.0 368.4 73.8 4.4 350.3 83.0 3.7 329.5 93.5 3.2 309.4 105.3 2.7 290.3 118.2 2.3 250.3 121.9 1.9
10.0 378.9 73.7 4.5 360.3 82.9 3.9 339.3 93.4 3.3 318.9 105.2 2.8 299.5 117.9 2.3 253.9 119.6 2.0
11.0 389.8 73.5 4.6 370.3 82.8 4.0 349.3 93.4 3.4 328.5 105.0 2.8 309.0 117.7 2.4 257.2 117.5 2.0
12.0 400.7 73.4 4.8 380.5 82.8 4.1 359.3 93.3 3.5 338.3 105.0 2.9 318.5 117.6 2.5 260.5 115.5 2.1
13.0 411.7 73.3 4.9 390.6 82.7 4.2 369.6 93.3 3.6 348.2 105.0 3.0 328.1 117.6 2.6 263.6 113.7 2.1
MODEL YCAS0118EB
5.0 404.4 96.1 3.8 380.3 108.3 3.2 356.2 122.2 2.7 333.4 137.8 2.2 312.2 155.1 1.9 241.0 145.0 1.6
6.0 416.3 96.4 3.9 392.2 108.6 3.3 367.6 122.5 2.8 344.4 137.9 2.3 322.9 155.0 2.0 244.6 142.4 1.6
7.0 428.3 96.7 4.0 404.1 108.8 3.4 379.1 122.7 2.8 355.5 138.1 2.4 333.6 155.0 2.0 249.3 140.4 1.7
8.0 440.3 96.9 4.1 416.1 109.1 3.5 390.8 122.9 2.9 366.8 138.2 2.5 340.7 153.0 2.1 252.9 138.1 1.7
9.0 453.0 97.2 4.2 428.1 109.4 3.6 402.7 123.1 3.0 378.2 138.4 2.5 348.1 151.1 2.2 256.3 135.9 1.8
10.0 465.7 97.4 4.3 440.3 109.7 3.7 414.6 123.4 3.1 389.7 138.6 2.6 355.4 149.5 2.2 259.6 133.8 1.8
11.0 478.7 97.6 4.4 452.6 110.0 3.8 426.6 123.7 3.2 401.4 138.9 2.7 362.4 147.7 2.3 262.8 131.9 1.8
12.0 491.7 97.8 4.5 464.9 110.2 3.8 438.7 124.0 3.3 413.2 139.2 2.8 369.5 146.1 2.4 265.9 130.0 1.9
13.0 504.8 98.1 4.6 477.5 110.5 3.9 451.0 124.3 3.3 425.1 139.5 2.8 376.5 144.6 2.4 268.8 128.2 1.9
MODEL YCAS0128EB
5.0 427.9 88.0 4.2 401.6 99.0 3.5 375.8 111.7 3.0 351.1 125.9 2.5 326.2 143.0 2.1 298.0 156.7 1.7
6.0 441.0 88.0 4.3 414.0 99.0 3.7 387.9 111.6 3.1 360.8 126.9 2.6 337.4 142.7 2.2 305.8 154.8 1.8
7.0 452.5 88.5 4.4 426.4 99.1 3.8 398.4 112.4 3.1 374.4 125.8 2.7 348.8 142.4 2.2 313.0 152.8 1.9
8.0 465.9 88.4 4.5 437.8 99.6 3.8 410.9 112.3 3.2 384.8 126.5 2.7 360.4 142.2 2.3 320.2 150.9 1.9
9.0 479.4 88.3 4.7 450.5 99.6 4.0 423.5 112.3 3.3 396.9 126.4 2.8 372.1 142.0 2.4 327.4 149.1 2.0
10.0 492.8 88.3 4.8 463.5 99.5 4.1 436.2 112.2 3.5 409.2 126.4 2.9 383.9 141.9 2.5 334.5 147.4 2.1
11.0 506.2 88.2 4.9 476.9 99.5 4.2 449.1 112.2 3.6 421.6 126.4 3.0 395.8 141.9 2.5 341.6 145.8 2.1
12.0 519.9 88.1 5.1 490.5 99.5 4.3 462.0 112.2 3.7 434.1 126.4 3.1 407.9 141.9 2.6 348.6 144.3 2.2
13.0 533.4 88.1 5.2 504.1 99.5 4.4 475.0 112.3 3.8 446.8 126.5 3.2 420.2 141.9 2.7 355.8 143.0 2.3
NOTES:
1. kWo = Unit kW Cooling Capacity Output
2. kW
i
= Compressor kW Input
3. COP = Coefcient of Performance (includes condenser fan power)
4. LCWT = Leaving Chilled Water Temperature
5. Ratings based on 0.15 l/s cooler water per ton.