Unitary Products Group 19
TABLE 11: ELECTRIC HEAT CORRECTION
FACTORS
NOMINAL VOLTAGE VOLTAGE kW CAP. MULTIPLIER
208
208 0.75
240
230 0.92
480
460 0.92
600
575 0.92
TABLE 12: VOLTAGE LIMITATIONS
1
1.
Utilization Range “A” in accordance with ARI Standard
110.
POWER SUPPLY
VOLTAGE
MIN. MAX.
208/230-3-60
187 253
460-3-60
414 506
575-3-60
518 630
FIGURE 7: UNIT DIMENSIONS (3 - 5 TON HEAT PUMP) FRONT VIEW