036-21539-003-B-0305
28 Unitary Products Group
TABLE 12: COOLING CAPACITIES FOR DR240 AT 85°F (ALTERNATE REHEAT MODE)
AIR ON
EVAPORATOR COIL
TEMPERATURE OF AIR ON CONDENSER COIL (°F): 85
CFM
WB
°F
TOTAL
CAPACITY
1
(MBH)
TOTAL
INPUT
2
(kW)
SENSIBLE CAPACITY
1
(MBH)
RETURN DRY BULB (°F)
86 83 80 77 74 71
6000
67
100 18.0 44 27 10
62
90 17.4 60 43 26 9
57
85 17.1 65 48 31 14
6875
67
107 17.9 59 39 19
62
96 17.3 81 71 51 31 11
57
90 17.0 80 72 60 41 21 1
7750
67
113 17.8 74 51 28 6
62
102 17.3 102 99 76 54 31 9
57
95 17.0 95 95 90 68 45 22
8725
67
111 17.9 78 52 27 1
62
100 17.4 100 98 72 46 20
57
94 17.1 94 94 85 59 33
9400
67
110 18.0 83 54 25
62
99 17.5 99 96 67 38 9
57
93 17.1 93 93 79 50 22
1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBH = 3.415 x kW. Refer to the appropriate blower
performance table for the kW of the supply air blower motor.
2. These ratings include condensate fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
No Sensible Cooling Capacity
TABLE 13: COOLING CAPACITIES FOR DR240 AT 95°F (ALTERNATE REHEAT MODE)
AIR ON
EVAPORATOR COIL
TEMPERATURE OF AIR ON CONDENSER COIL (°F): 95
CFM
WB
°F
TOTAL
CAPACITY
1
(MBH)
1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBH = 3.415 x kW. Refer to the appropriate blower
performance table for the kW of the supply air blower motor.
TOTAL
INPUT
2
(kW)
2. These ratings include condensate fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
SENSIBLE CAPACITY
1
(MBH)
RETURN DRY BULB (°F)
86 83 80 77 74 71
6000
67
93 18.8 39 22 5
62
84 18.2 51 34 17
57
80 18.0 54 36 19 2
6875
67
98 18.7 53 33 13
62
89 18.1 72 64 44 24 4
57
84 17.9 71 63 51 31 11
7750
67
104 18.6 67 44 21
62
94 18.1 94 94 71 49 26 3
57
89 17.8 89 89 83 60 37 15
8725
67
100 18.7 71 45 19
62
91 18.2 91 89 64 38 12
57
86 17.9 86 86 74 48 22
9400
67
97 18.8 75 46 17
62
88 18.3 88 85 56 27
57
83 18.0 83 83 65 36 7
No Sensible Cooling Capacity