036-21539-003-B-0305
Unitary Products Group 29
TABLE 14: COOLING CAPACITIES FOR DR240 AT 105°F (ALTERNATE REHEAT MODE)
AIR ON
EVAPORATOR COIL
TEMPERATURE OF AIR ON CONDENSER COIL (°F): 105
CFM
WB
°F
TOTAL
CAPACITY
1
(MBH)
TOTAL
INPUT
2
(kW)
SENSIBLE CAPACITY
1
(MBH)
RETURN DRY BULB (°F)
86 83 80 77 74 71
6000
67
46 9.4 20 11 3
62
42 9.1 25 17 8
57
40 9.0 27 18 10
6875
67
70 14.5 40 24 9
62
64 14.1 56 51 37
57
61 13.9 54 50 42
7750
67
95 19.6 60 38 15
62
86 19.0 86 86 66 44 21
57
82 18.8 82 82 75 52 30 7
8725
67
72 14.5 49 30 12
62
65 14.1 65 64 47 21
57
62 13.9 62 62 54 28 2
9400
67
48 9.4 37 23 8
62
44 9.1 44 42 28
57
42 9.0 42 42 32 4
1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBH = 3.415 x kW. Refer to the appropriate blower
performance table for the kW of the supply air blower motor.
2. These ratings include condensate fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
No Sensible Cooling Capacity
TABLE 15: COOLING CAPACITIES FOR DR240 AT 115°F (ALTERNATE REHEAT MODE)
AIR ON
EVAPORATOR COIL
TEMPERATURE OF AIR ON CONDENSER COIL (°F): 115
CFM
WB
°F
TOTAL
CAPACITY
1
(MBH)
1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBH = 3.415 x kW. Refer to the appropriate blower
performance table for the kW of the supply air blower motor.
TOTAL
INPUT
2
(kW)
2. These ratings include condensate fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
SENSIBLE CAPACITY
1
(MBH)
RETURN DRY BULB (°F)
86 83 80 77 74 71
6000
67
62
57
6875
67
43 10.3 27 16 4
62
39 10.0 39 39 31 11
57
38 9.9 38 38 34 14
7750
67
86 20.6 54 31 9
62
78 20.0 78 78 62 39 17
57
75 19.9 75 75 68 45 22
8725
67
43 10.3 27 16 4
62
39 10.0 39 39 31 5
57
38 9.9 38 38 34 8
9400
67
62
57
No Sensible Cooling Capacity

Table of Contents

Related product manuals