036-21539-003-B-0305
Unitary Products Group 49
NOTE 1: HACR Type per NEC.
TABLE 34: DR ELECTRICAL DATA - LOW AIRFLOW DRIVE MOTOR W/O POWERED CONVENIENCE OUTLET
MODEL
TONNAGE
VOLTAGE
COMPRESSORS
OD FAN
MOTORS
FLA EACH
ID
BLOWER
MOTOR
FLA
CONV
OUTLET
AMPS
HEATER OPTION
MIN.
CIRCUIT
AMPACITY
(AMPS)
MAX. FUSE/
BRKR
1
SIZE
(AMPS)
RLA
EACH
LRA
EACH
MODEL KW STAGES AMPS
25
208 47.1 245 3.7 20.0 0.0
None 0.0 ~ ~ 140.8 175
E18 13.5 1 37.5 140.8 175
E36 27.0 2 75.1 140.8 175
E54 40.6 2 112.6 165.9 175
E72 54.1 2 150.1 175.2 200
230 47.1 245 3.7 20.0 0.0
None 0.0 ~ ~ 140.8 175
E18 18.0 1 43.3 140.8 175
E36 36.0 2 86.6 140.8 175
E54 54.0 2 129.9 154.9 175
E72 72.0 2 173.2 198.2 225
460 19.6 125 1.9 10.0 0.0
None 0.0 ~ ~ 61.7 80
E18 18.0 1 21.7 61.7 80
E36 36.0 2 43.3 66.6 80
E54 54.0 2 65.0 77.5 90
E72 72.0 2 86.6 99.1 110
575 15.8 100 1.5 8.2 0.0
None 0.0 ~ ~ 49.8 60
E18 18.0 1 17.3 49.8 60
E36 36.0 2 34.6 53.6 60
E54 54.0 2 52.0 62.2 70
E72 72.0 2 69.3 79.5 90
VOLTAGE LIMITATIONS ELECTRIC HEAT CORRECTION FACTORS
POWER SUPPLY
VOLTAGE NOMINAL VOLTAGE VOLTAGE kW CAP. MULTIPLIER
MIN. MAX. 208 208 1.00
VOLTAGE
LIMITATIONS
1
208/230-3-60 187 253 240 230 0.92
460-3-60 414 506 480 460 0.92
565-3-60 518 630 600 575 0.92
1. Utilization Range “A” in accordance with ARI Standard 110.