5188235-YIM-E-0518
18 Johnson Controls Ducted Systems
060
(5.0)
208-1-60 24.4 144.2 38 4.4 6.7 0
NONE - - - 41.6 50
E05 4 1 19.2 41.6 50
E07 5.6 1 26.9 42 60
E10 8 1 38.5 56.5 60
E15 11.9 2 57.2 79.9 80
E20 15.9 2 76.4 103.9 110
E30 22.2 2 106.7 141.8 150
230-1-60 24.4 144.2 38 4.4 6.7 0
NONE - - - 41.6 50
E05 5.3 1 22.1 41.6 50
E07 7.5 1 31.2 47.4 60
E10 10.6 1 44.2 63.6 70
E15 15.9 2 66.2 91.2 100
E20 21.2 2 88.3 118.8 125
E30 29.6 2 123.3 162.5 175
208-3-60 16 110 24.9 4.4 4.3 0
NONE - - - 28.7 35
E05 4 1 11.1 28.7 35
E07 5.6 1 15.5 28.7 35
E10 8 1 22.2 33.1 40
E15 11.9 2 33 46.7 50
E20 15.9 2 44.1 60.5 70
E30 22.2 2 61.6 82.4 90
230-3-60 16 110 24.9 4.4 4.3 0
NONE - - - 28.7 35
E05 5.3 1 12.7 28.7 35
E07 7.5 1 18 28.7 35
E10 10.6 1 25.5 37.2 40
E15 15.9 2 38.2 53.2 60
E20 21.2 2 51 69.1 70
E30 29.6 2 71.2 94.4 100
460-3-60 7.8 52 12.1 4.4 2.1 0
NONE - - - 14.1 20
E07 6.8 1 8.2 14.1 20
E10 10.1 1 12.1 17.8 20
E15 13.6 2 16.4 23.1 25
E20 19.5 2 23.5 31.9 35
E30 28.8 2 34.6 45.9 50
575-3-60 5.7 38.9 8.9 4.4 1.9 0
NONE - - - 10.8 15
E10 10.6 1 10.2 15.1 20
E15 15.9 2 15.3 21.5 25
E20 21.2 2 20.4 27.9 30
E30 30.4 2 29.3 38.9 40
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
ZE036-060 - Without Powered Convenience Outlet (Belt Drive) (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC FLA FLA FLA Model kW Stages Amps