EasyManua.ls Logo

York Sunline ZE Series - Electrical Data: Direct Drive Continued

York Sunline ZE Series
77 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5188235-YIM-E-0518
22 Johnson Controls Ducted Systems
060
(5.0)
208-1-60 24.4 144.2 38 4.4 7.6 0
NONE - - - 42.5 60
E05 4 1 19.2 42.5 60
E07 5.6 1 26.9 43.2 60
E10 8 1 38.5 57.6 60
E15 11.9 2 57.2 81 90
E20 15.9 2 76.4 105.1 110
E30 22.2 2 106.7 142.9 150
230-1-60 24.4 144.2 38 4.4 7.6 0
NONE - - - 42.5 60
E05 5.3 1 22.1 42.5 60
E07 7.5 1 31.2 48.6 60
E10 10.6 1 44.2 64.7 70
E15 15.9 2 66.2 92.3 100
E20 21.2 2 88.3 119.9 125
E30 29.6 2 123.3 163.7 175
208-3-60 16 110 24.9 4.4 7.6 0
NONE - - - 32 40
E05 4 1 11.1 32 40
E07 5.6 1 15.5 32 40
E10 8 1 22.2 37.3 45
E15 11.9 2 33 50.8 60
E20 15.9 2 44.1 64.7 70
E30 22.2 2 61.6 86.5 90
230-3-60 16 110 24.9 4.4 7.6 0
NONE - - - 32 40
E05 5.3 1 12.7 32 40
E07 7.5 1 18 32.1 40
E10 10.6 1 25.5 41.4 45
E15 15.9 2 38.2 57.3 60
E20 21.2 2 51 73.2 80
E30 29.6 2 71.2 98.5 100
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
ZE036-060 - Without Powered Convenience Outlet (Direct Drive) (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC FLA FLA FLA Model kW Stages Amps

Table of Contents

Related product manuals