5188235-YIM-E-0518
26 Johnson Controls Ducted Systems
060
(5.0)
208-3-60 16 110 24.9 4.4 6.8 10
NONE - - - 41.2 50
E05 4 1 11.1 41.2 50
E07 5.6 1 15.5 41.2 50
E10 8 1 22.2 48.8 50
E15 11.9 2 33 62.3 70
E20 15.9 2 44.1 76.2 80
E30 22.2 2 61.6 98 100
230-3-60 16 110 24.9 4.4 6.8 10
NONE - - - 41.2 50
E05 5.3 1 12.7 41.2 50
E07 7.5 1 18 43.6 50
E10 10.6 1 25.5 52.9 60
E15 15.9 2 38.2 68.8 70
E20 21.2 2 51 84.7 90
E30 29.6 2 71.2 110 125
460-3-60 7.8 52 12.1 4.4 3.15 5
NONE - - - 20.1 25
E07 6.8 1 8.2 20.4 25
E10 10.1 1 12.1 25.4 30
E15 13.6 2 16.4 30.6 35
E20 19.5 2 23.5 39.5 40
E30 28.8 2 34.6 53.5 60
575-3-60 5.7 38.9 8.9 4.4 2.2 4
NONE - - - 15.1 20
E10 10.6 1 10.2 20.5 25
E15 15.9 2 15.3 26.9 30
E20 21.2 2 20.4 33.2 35
E30 30.4 2 29.3 44.3 45
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
ZE036-060 - With Powered Convenience Outlet (Belt Drive High Static) (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC FLA FLA FLA Model kW Stages Amps