5371951-YTG-C-0919
20 Johnson Controls Ducted Systems
MECHANICAL SPECIFICATIONS
MANUFACTURE AND CERTIFICATIONS
Units shall be manufactured in an ISO 9001 certified facility.
Units shall be certified by CSA to UL 1995 / CSA 22.2 and
performance certified to ANSI/AHRI Standard 210/240.
Units shall be sound tested according to ANSI/AHRI Stan-
dard 270.
Certified matched system ratings will be available for down-
load from the AHRI online directory at www.ahridirectory.org
Unit packaging shall be marked, “Assembled in the USA”
UNIT APPLICATION
Units shall be approved for cooling operation between 50ºF
and 120ºF without modification.
Units shall be approved for linesets up to 200 feet equivalent
length without modification.
Units shall be approved for installation within 6 inches of a
flat vertical wall without modification, according to the
instructions in the technical literature.
Units shall be certified for seismic applications in accordance
with CBC 2007 and IBC 2006.
Units shall be designed to 72dBA or less to minimize sound
pollution.
UNIT ACCESS
Units shall have a fan guard that can be removed inde-
pendently of the cabinet for access to the condenser coil.
Units shall have blow-through airflow for the condensing coil.
Units shall have a separate compartment for electrical con-
trols that can be accessed without disturbing the unit airflow.
UNIT CONSTRUCTION
Units shall be shipped completely wired, piped and assem-
bled. Wiring pigtails shall be provided for field control wiring
connections. Service valves shall be provided for field refrig-
erant line connections.
Units shall be factory leak checked, run tested, and shipped
with a holding charge of R-410A refrigerant.
Unit cabinet components shall be G90 equivalent steel fin-
ished with powder-coat paint rated at a minimum of 1,000
hours under ASTM B117 testing.
Unit base pan shall be stamped G90 equivalent steel fin-
ished with powder-coat paint rated at a minimum of 1,000
hours under ASTM B117 testing.
Units shall have a factory installed filter drier for faster instal-
lation and improved system reliability.
Units shall be constructed with a high pressure switch and a
low pressure switch for system protection.
UNIT COMPONENTS
Compressor shall be hermetic with internal electrical over-
load protection and internal overpressure protection.
Compressor shall be mounted on rubber vibration isolators
that do not require the removal of transportation clips or
brackets.
Units shall be constructed with scroll compressors.
Outdoor fan shall be direct drive with horizontal air dis-
charge.
Outdoor fan shall be direct drive with swept-wing blades for
low sound levels.
Outdoor coil shall be air cooled and constructed of zinc-
coated aluminum microchannel construction for small size
and low weight.
UNIT WARRANTIES
Unit manufacturer shall provide a 10-Year compressor war-
ranty without a requirement for unit registration.
Unit manufacturer shall provide a 5-Year parts warranty with-
out a requirement for unit registration.