JOHNSON CONTROLS
21
FORM 150.62-EG1 (507)
NOTES:
1. kWo = Unit kW Cooling Capacity Output
2. kWi = Compressor kW Input
3. COP = Coefcient of Performance (Based upon compressor and fan input kW)
4. LCWT = Leaving Chilled Water Temperature
5. Ratings based upon 0.15L/s cooler water per kW
YCAL0104EC
YCAL0124EC
YCAL0114EC
COP=4.01
COP=4.12
COP=3.96
AIR TEMPERATURE ON - CONDENSER (°C)
LCWT 25°C 30°C 35°C 40°C 45°C 50°C
(°C) kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP
5.0
363.3 90.8 3.6 348.5 99.5 3.2 332.7 109.2 2.8 316.2 120.2 2.4 299.1 132.6 2.1 236.5 112.9 1.9
6.0
375.3 91.8 3.7 359.4 100.4 3.2 343.2 110.2 2.8 326.3 121.3 2.5 308.7 133.7 2.1 244.3 113.7 2.0
7.0
386.8 92.8 3.7 370.7 101.4 3.3 354.0 111.2 2.9 336.6 122.4 2.5 318.7 134.9 2.2 252.5 114.6 2.0
8.0
398.7 93.8 3.8 382.1 102.5 3.4 365.0 112.3 3.0 347.2 123.5 2.6 329.0 136.0 2.2 260.5 115.5 2.1
9.0
410.9 94.9 3.9 393.8 103.5 3.4 376.2 113.4 3.0 358.1 124.6 2.6 339.3 137.3 2.3 268.9 116.4 2.1
10.0
423.2 96.0 4.0 405.7 104.6 3.5 387.6 114.6 3.1 369.1 125.8 2.7 349.9 138.5 2.3 277.8 117.4 2.2
11.0
435.8 97.1 4.0 417.8 105.8 3.6 399.3 115.7 3.2 380.3 127.0 2.8 360.7 139.7 2.4 286.6 118.3 2.2
AIR TEMPERATURE ON - CONDENSER (°C)
LCWT 25°C 30°C 35°C 40°C 45°C 50°C
(°C) kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP
5.0
403.7 99.1 3.6 387.4 108.6 3.2 370.7 119.4 2.8 352.9 131.5 2.4 334.0 145.1 2.1 313.8 160.6 1.8
6.0
416.4 100.1 3.6 399.7 109.6 3.2 382.5 120.4 2.8 364.4 132.5 2.5 345.1 146.3 2.2 324.4 161.8 1.8
7.0
429.5 101.1 3.7 412.3 110.6 3.3 394.6 121.4 2.9 376.1 133.6 2.5 356.4 147.5 2.2 335.4 163.0 1.9
8.0
442.8 102.1 3.8 425.2 111.7 3.4 407.0 122.5 3.0 388.0 134.8 2.6 367.9 148.6 2.3 346.5 164.3 1.9
9.0
456.5 103.1 3.9 438.3 112.7 3.5 419.7 123.6 3.0 400.2 135.9 2.7 379.6 149.9 2.3 357.8 165.6 2.0
10.0
470.4 104.1 4.0 451.8 113.8 3.5 432.6 124.8 3.1 412.7 137.1 2.7 391.7 151.1 2.4 369.3 166.9 2.0
11.0
484.8 105.2 4.1 465.6 114.9 3.6 445.9 125.9 3.2 425.4 138.4 2.8 403.9 152.4 2.4 380.9 168.4 2.1
AIR TEMPERATURE ON - CONDENSER (°C)
LCWT 25°C 30°C 35°C 40°C 45°C 50°C
(°C) kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP
5.0
440.9 109.9 3.6 422.7 120.3 3.1 400.6 131.7 2.7 384.5 145.1 2.4 364.5 159.8 2.1 343.9 176.1 1.8
6.0
454.7 111.0 3.6 435.9 121.4 3.2 416.7 133.1 2.8 396.8 146.4 2.5 376.2 161.2 2.1 297.3 140.1 1.9
7.0
468.8 112.2 3.7 449.5 122.6 3.3 429.7 134.4 2.9 409.3 147.7 2.5 388.1 162.4 2.2 307.2 141.1 2.0
8.0
483.2 113.3 3.8 463.4 123.8 3.4 443.0 135.6 3.0 422.1 149.0 2.6 400.9 163.8 2.3 317.4 142.2 2.0
9.0
497.8 114.5 3.9 477.5 125.0 3.4 456.6 136.9 3.0 435.3 150.2 2.6 413.5 165.2 2.3 327.7 143.2 2.1
10.0
512.8 115.8 3.9 491.9 126.2 3.5 470.6 138.1 3.1 448.8 151.5 2.7 426.4 166.6 2.4 338.1 144.4 2.1
11.0
528.2 117.0 4.0 506.7 127.5 3.6 484.9 139.3 3.2 462.4 152.9 2.8 439.5 168.0 2.4 348.8 145.5 2.2
YCAL0134EC
COP = 3.90
AIR TEMPERATURE ON - CONDENSER (C)
LCWT 25
o
C 30
o
C 35
o
C 40
o
C 45
o
C 50
o
C
(
o
C) kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP
5.0
476.4 121.9 3.5 456.1 133.2 3.1 435.4 146.1 2.7 414.4 160.3 2.4 393.0 176.2 2.1 372.6 193.5 1.8
6.0
491.1 123.1 3.6 470.3 134.5 3.2 449.0 147.4 2.8 427.5 161.8 2.4 405.8 177.8 2.1 268.8 119.5 2.0
7.0
506.1 124.5 3.6 484.8 135.8 3.2 463.0 148.7 2.8 440.8 163.3 2.5 418.9 179.3 2.2 277.6 120.4 2.1
8.0
521.4 125.8 3.7 499.5 137.2 3.3 477.0 150.1 2.9 454.4 164.8 2.5 432.1 180.8 2.2 286.7 121.2 2.1
9.0
537.1 127.2 3.8 514.6 138.5 3.4 491.6 151.6 3.0 468.7 166.1 2.6 445.5 182.3 2.3 295.9 122.1 2.2
10.0
553.3 128.7 3.9 530.0 140.0 3.4 506.6 152.9 3.0 483.0 167.5 2.7 459.3 183.9 2.3 305.2 122.9 2.2
11.0
569.0 130.1 3.9 545.7 141.4 3.5 521.8 154.3 3.1 497.6 169.0 2.7 473.3 185.5 2.4 314.9 123.8 2.3