Dimensions -YCAL0064-YCAL0080 (SI)
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reli-
able operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable
airow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety
cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit
is no higher than on spring isolators. Recommended minimum clearances: Side to wall – 2m; rear to wall – 2m; control panel to end wall
1.2m; top no obstructions allowed; distance between adjacent units 3m. No more than one adjacent wall may be higher than the
unit.
LD04878
2311
759 (EDGE OF
UNIT TO COOLER
CONNECTION)
403
VIEW A-A
51
38
76
321
127
127
76
38
76
CONTROL ENTRY
(8) 13 CONDUIT K.O.'S
98
25 TYP.
B B
VIEW B-B
POWER ENTRY
(2) 64,51,38 CONDUIT K.O.'S
(5) 13 CONDUIT K.O.'S
102
NOTE: All dimensions are in mm unless specied otherwise.
HFC-407c for YCAL0064 and YCAL0070 models only