SECTION 2 – PRODUCT DESCRIPTION
SINGLE-POINT CIRCUIT BREAKERA unit
mounted circuit breaker with external, lockable handle
(in compliance with N.E.C. Article 440-14), can be
supplied to isolate the power voltage for servicing (this
option includes the Single-Point Power connection).
CONTROL TRANSFORMER – Converts unit pow-
er voltage to 115-1-60 (0.5 or 1.0 KVA capacity). Fac-
tory mounting includes primary and secondary wiring
between the transformer and the control panel (Facto-
ry-Mounted).
POWER FACTOR CORRECTION CAPACI-
TORSWill correct unit compressor power factors to
a 0.90-0.95 (Factory-Mounted).
Control Options
AMBIENT KIT (LOW) – Units will operate to 25 °F
(-4 °C). This accessory includes all necessary compo-
nents to permit chiller operation to 0 °F (-18 °C). (This
option includes the Discharge Pressure Transducer /
Readout Capability option). For proper head pressure
control in applications below 25 °F (-4 °C), where
wind gusts may exceed five mph, it is recommended
that Optional Condenser Louvered Enclosure Panels
also be included (Factory-Mounted).
AMBIENT KIT (HIGH) – Required if units are to
operate when the ambient temperature is above 110 °F
(43 °C). Includes discharge pressure transducers. (This
option includes the Discharge Pressure Transducer /
Readout Capability option) (Field-Mounted).
BUILDING AUTOMATION SYSTEM INTER-
FACE – The factory addition of a Printed Circuit
Board to accept a 4-20 milliamp, 0-10VDC or contact
closure input to reset the leaving chiller liquid tem-
perature from a Building Automation System. (Only
one of following options can be offered on a unit at
a time: BAS, Remote Control Panel or Multi-unit Se-
quence Control) (Factory-Mounted). (The standard
unit capabilities include remote startstop, remote water
temperature reset via a PWM input signal or up to two
steps of demand (load) limiting depending on model).
(The standard control panel can be directly connected
to a YORK Building Automated System via the stan-
dard onboard RS485 communication port).
LANGUAGE LCD AND KEYPAD DISPLAY
Spanish, French, and German unit LCD controls and
keypad displays are available. Standard language is
English.
DISCHARGE PRESSURE TRANSDUCERS AND
READOUT CAPABILITY – The addition of pres-
sure transducers allows models to sense and display
discharge pressure. This is recommended for brine
chilling applications. (This option is included with ei-
ther the low or high ambient kits) (Factory-Mounted).
Suction Pressure Transducers: Permits unit to
sense and display suction pressure. This capabil-
ity is standard on YCAL0019-0066 models.
MOTOR CURRENT MODULE – Capable of moni-
toring compressor motor current. Provides extra pro-
tection against compressor reverse rotation, phase-loss
and phase imbalance. Option consists of one module
per electrical system (Factory-Mounted).
MULTI-UNIT SEQUENCINGA separate Sequenc-
ing Control Center can be provided to handle sequenc-
ing control of up to eight chillers in parallel based on
mixed liquid temperature (interconnecting wiring by
others). (Only one of following options can be offered
on a unit at a time: BAS, Remote ControSl Panel or
Multi-unit Sequence Control) (Factory-Mounted).
COMPRESSOR, PIPING, EVAPORATOR
OPTIONS
LOW TEMPERATURE BRINE – Required for brine
chilling below 30 °F (-1 °C) leaving brine temperature
for YCAL0019 – 0066 models. Option includes resized
thermal expansion valve (Factory-Mounted).
CHICAGO CODE RELIEF VALVES – Unit will be
provided with relief valves to meet Chicago code re-
quirements (Factory-Mounted).
SERVICE ISOLATION VALVE – Service suction
and discharge (ball type) isolation valves are added to
unit per system. This option also includes a system high
pressure relief valve in compliance with ASHRAE 15
(Factory-Mounted).
HOT GAS BY-PASS – Permits continuous, stable op-
eration at capacities below the minimum step of com-
pressor unloading to as low as 5% capacity (depending
on both the unit and operating conditions) by introduc-
ing an artificial load on the cooler. Hot gas by-pass is
installed on only refrigerant system #1 on two-circuit-
ed units (Factory-Mounted).