SECTION 5 – TECHNICAL DATA
FORM 150.67-NM2
ISSUE DATE: 01/31/2019
5
TABLE 9 - ELECTRICAL DATA (ENGLISH)
Model
YCAL
VOLT
50 Hz
MCA
1
MIN
N/F
DISC
MDSW
2
D.E. Fuse CKT. BKR.
5
FIELD WIRING LUGS
TERMINAL BLOCK (std)
FIELD WIRING LUGS NF
DISC SWITCH (opt)
FIELD WIRING LUGS
CIRCUIT BREAKER (opt)
SYSTEM #1 COMPRESSOR and FAN SYSTEM #2 COMPRESSOR and FAN
COMPR. #1 COMPR. #2 FANS COMPR. #1 COMPR. #2 FANS
Min. MAX
4
MIN. MAX
LUGS/
PHASE
LUG WIRE
RANGE
LUGS/
PHASE
LUG WIRE
RANGE
LUGS/
PHASE
LUG WIRE
RANGE
RLA LRA RLA LRA QTY FLA RLA RLA LRA RLA LRA QTY FLA RLA
0019 400 45 60 50 60 50 60 1
14 AWG-2/0,
PB-0800
1 14 AWG -1/0 1 14 AWG -1/0 18.6 114 18.6 114 2 1.3 2.5 - - - - - - -
0022 400 48 60 60 60 60 60 1
14 AWG-2/0,
PB-0800
1 14 AWG -1/0 1 14 AWG -1/0 20.0 125 20.0 125 2 1.3 2.5 - - - - - - -
0028 400 58 100 70 80 70 80 1
14 AWG-2/0,
PB-0800
1 14 AWG -1/0 1 14 AWG -1/0 21.8 140 23.7 198 2 3.4 17.5 - - - - - - -
0033 400 68 100 80 90 80 90 1
14 AWG-2/0,
PB-0800
1 14 AWG -1/0 1 14 AWG -1/0 26.4 198 26.4 198 2 4.0 19.0 - - - - - - -
0043 400 102 150 110 110 110 110 1
14 AWG-2/0,
PB-0800
1 4 AWG -300kcmil 1 6 AWG-350MCM 20.0 125 20.0 125 2 4.0 19.0 20.0 125 20.0 125 2 4.0 19.0
0046 400 103 150 110 110 110 110 1
14 AWG-2/0,
PB-0800
1 4 AWG -300kcmil 1 6 AWG-350MCM 20.7 125 20.7 125 2 4.0 19.0 20.0 125 20.0 125 2 4.0 19.0
0052 400 106 150 125 125 125 125 1
14 AWG-2/0,
PB-0800
1 4 AWG -300kcmil 1 6 AWG-350MCM 21.8 140 21.8 140 2 3.4 17.5 21.8 140 21.8 140 2 3.4 17.5
0056 400 114 150 125 125 125 125 1
14 AWG-2/0,
PB-0800
1 4 AWG -300kcmil 1 6 AWG-350MCM 23.7 198 23.7 198 2 3.4 17.5 23.7 198 23.7 198 2 3.4 17.5
0066 400 146 200 175 175 175 175 1
6 AWG-350kcmil,
PB-0801
1 6 AWG -350kcmil 1 6 AWG-350MCM 33.9 225 33.9 225 2 4.0 19.0 26.4 198 26.4 198 2 4.0 19.0
SINGLE POINT FIELD SUPPLIED POWER WIRING (See Fig. 8)
(One Field Provided Power Supply to the chiller. Field connections to Factory Provided Power Terminal Block (standard),
Non-Fused Disconnect Switch (optional) or Circuit Breaker (optional)).