York YCAQ10 - LWT CONTROL LOADING;UNLOADING; LOADING;UNLOADING STAGES BY COOLING RANGE

York YCAQ10
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
30 YORK INTERNATIONAL
SINGLE CIRCUIT UNITS
COOLING RANGE
SWITCH = 3
COOLING RANGE
OF
+1.5°F ( +.83°C)
STAGE ON OFF
Loader Stage 4 Setpoint plus 1.5°F (.83°C) Setpoint plus 0.8°F (.44°C)
Loader Stage 3 Setpoint plus 0.7°F (.38°C) Setpoint
Loader Stage 2 Setpoint Setpoint minus 0.8°F (.44°C)
Compressor Stage 1 Setpoint minus 0.7°F (.38°C) Setpoint minus 1.5°F (.83°C)
STAGE ON OFF
Loader Stage 4 Setpoint plus 1.6°F (.88°C) Setpoint plus 0.8°F (.44°C)
Loader Stage 3 Setpoint plus 0.8°F (.44°C) Setpoint
Loader Stage 2 Setpoint Setpoint minus 0.8°F (.44°C)
Compressor Stage 1 Setpoint minus 0.8°F (.44°C) Setpoint minus 1.6°F (.88°C)
STAGE ON OFF
Loader Stage 4 Setpoint plus 1.8°F (.99°C) Setpoint plus 0.9°F (.49°C)
Loader Stage 3 Setpoint plus 0.9°F (.49°C) Setpoint
Loader Stage 2 Setpoint Setpoint minus 0.9°F (.49°C)
Compressor Stage 1 Setpoint minus 0.9°F (.49°C) Setpoint minus 1.8°F (.99°C)
COOLING RANGE
SWITCH = 5
COOLING RANGE
OF
+1.8°F ( +.99°C)
COOLING RANGE
SWITCH = 4
COOLING RANGE
OF
+1.6°F (+.88°C)
COOLING RANGE
SWITCH = 6
COOLING RANGE
OF
+1.9°F ( +1.05°C)
STAGE ON OFF
Loader Stage 4 Setpoint plus 1.9°F (1.05°C) Setpoint plus 1.1°F (.61°C)
Loader Stage 3 Setpoint plus 1.1°F (.61°C) Setpoint
Loader Stage 2 Setpoint Setpoint minus 1.1°F (.61°C)
Compressor Stage 1 Setpoint minus 1.0°F (.55°C) Setpoint minus 1.9°F (1.05°C)
STAGE ON OFF
Loader Stage 4 Setpoint plus 2.0°F (1.11°C) Setpoint plus 1.0°F (.55°C)
Loader Stage 3 Setpoint plus 1.0°F (.55°C) Setpoint
Loader Stage 2 Setpoint Setpoint minus 1.0°F (.55°C)
Compressor Stage 1 Setpoint minus 1.0°F (.55°C) Setpoint minus 2.0°F (1.11°C)
COOLING RANGE
SWITCH = 7
COOLING RANGE
OF
+2.0°F (+1.11°C)