YORK INTERNATIONAL 65
FORM 150.40-NM25
STAGE ON OFF
Lag Compr. Loader Stage 2 Setpoint plus 1.2°F (.66°C) Setpoint plus 0.6°F (.33°C)
Lag Compressor (Stage 1) Setpoint plus 0.6°F (.33°C) Setpoint
Lead Compr. Loader Stage 2 Setpoint Setpoint minus 0.6°F (.33°C)
Lead Compressor (Stage 1) Setpoint minus 0.6°F (.33°C) Setpoint minus 1.2°F (.66°C)
COOLING RANGE
SWITCH = 1
COOLING RANGE
OF ± 1.2°F (± .66°C)
DUAL CIRCUIT UNITS
STAGE ON OFF
Lag Compr. Loader Stage 2 Setpoint plus 1.4°F (.77°C) Setpoint plus 0.7°F (.38°C)
Lag Compressor (Stage 1) Setpoint plus 0.7°F (.38°C) Setpoint
Lead Compr. Loader Stage 2 Setpoint Setpoint minus 0.7°F (.38°C)
Lead Compressor (Stage 1) Setpoint minus 0.7°F (.38°C) Setpoint minus 1.4°F (.77°C)
COOLING RANGE
SWITCH = 2
COOLING RANGE
OF ± 1.4°F (± .78°C)
STAGE ON OFF
Lag Compr. Loader Stage 2 Setpoint plus 1.5°F (.83°C) Setpoint plus 0.8°F (.44°C)
Lag Compressor (Stage 1) Setpoint plus 0.7°F (.38°C) Setpoint
Lead Compr. Loader Stage 2 Setpoint Setpoint minus 0.8°F (.44°C)
Lead Compressor (Stage 1) Setpoint minus 0.7°F (.38°C) Setpoint minus 1.5°F (.83°C)
COOLING RANGE
SWITCH = 3
COOLING RANGE
OF ± 1.5°F (± .83°C)
STAGE ON OFF
Lag Compr. Loader Stage 2 Setpoint plus 1.6°F (.88°C) Setpoint plus 0.8°F (.44°C)
Lag Compressor (Stage 1) Setpoint plus 0.8°F (.44°C) Setpoint
Lead Compr. Loader Stage 2 Setpoint Setpoint minus 0.8°F (.44°C)
Lead Compressor (Stage 1) Setpoint minus 0.8°F (.444°C) Setpoint minus 1.6°F (.88°C)
COOLING RANGE
SWITCH = 4
COOLING RANGE
OF ± 1.6°F (± .88°C)
STAGE ON OFF
Lag Compr. Loader Stage 2 Setpoint plus 1.8°F (.99°C) Setpoint plus 0.9°F (.49°C)
Lag Compressor (Stage 1) Setpoint plus 0.9°F (.49°C) Setpoint
Lead Compr. Loader Stage 2 Setpoint Setpoint minus 0.9°F (.49°C)
Lead Compressor (Stage 1) Setpoint minus 0.9°F (.49°C) Setpoint minus 1.8°F (.99°C)
COOLING RANGE
SWITCH = 5
COOLING RANGE
OF ± 1.8°F (± .99°C)
STAGE ON OFF
Lag Compr. Loader Stage 2 Setpoint plus 1.9°F (1.05°C) Setpoint plus 1.1°F (.61°C)
Lag Compressor (Stage 1) Setpoint plus 1.1°F (.61°C) Setpoint
Lead Compr. Loader Stage 2 Setpoint Setpoint minus 1.1°F (.61°C)
Lead Compressor (Stage 1) Setpoint minus 1.0°F (.55°C) Setpoint minus 1.9°F (1.05°C)
COOLING RANGE
SWITCH = 6
COOLING RANGE
OF ± 1.9°F (± 1.05°C)
STAGE ON OFF
Lag Compr. Loader Stage 2 Setpoint plus 2.0°F (1.11°C) Setpoint plus 1.0°F (.55°C)
Lag Compressor (Stage 1) Setpoint plus 1.0°F (.55°C) Setpoint
Lead Compr. Loader Stage 2 Setpoint Setpoint minus 1.0°F (.55°C)
Lead Compressor (Stage 1) Setpoint minus 1.0°F (.55°C) Setpoint minus 2.0°F (1.11°C)
COOLING RANGE
SWITCH = 7
COOLING RANGE
OF ± 2.0°F (± 1.11°C)