MODELS YCAV0267-0527, 60 HZ
STYLE A
(290-515 TONS)
AIR-COOLED SCREW LIQUID CHILLERS
E/V HIGH EFFICIENCY AND S/P STANDARD EFFICIENCY
50075
AIR-COOLED SCREW
LIQUID CHILLERS
INSTALLATION, OPERATION, MAINTENANCE Supersedes 201.21-NM3 (315) Form 201.21-NM3 (616)
035-20994-000
R134a
Issue Date:
June 30, 2016

Table of Contents

Questions and Answers

  • S
    scottnelsonAug 19, 2025
    What to do if York YCAV0357E has System Fault: LOW SUCTION PRESSURE?
    • J
      Joseph Jackson DVMAug 19, 2025
      If your York Chiller is showing a 'System Fault: LOW SUCTION PRESSURE', there are a couple of potential causes. It could be due to a low charge, in which case you should check the subcooling. Alternatively, the transducer might be reading incorrectly; compare its reading against a gauge.
  • C
    Carol OwensAug 21, 2025
    Why York YCAV0357E has no display on control panel and won't run?
    • G
      Gavin CrawfordAug 22, 2025
      If your York Chiller's control panel has no display and the unit won't run, the issue might stem from several causes: * The high voltage supply to the chiller could be missing. * A line fuse may be blown, so check the fuses. * The chiller control board could be defective, requiring replacement. * The display board itself might be defective, also requiring replacement.
  • P
    Phillip VincentAug 25, 2025
    What to do if my York YCAV0357E shows System Fault: HIGH OIL TEMPERATURE?
    • A
      Anthony AcostaAug 25, 2025
      If your York Chiller displays a 'System Fault: HIGH OIL TEMPERATURE' message, it could be due to several reasons. First, the oil temperature sensor might be defective; you can check it with infrared to see if the reading is reasonable. Second, the condenser fans might not be operating or are running backward, so check the fans. Lastly, the coils could be dirty; inspect and clean them if necessary.
  • D
    danielle20Aug 26, 2025
    What causes York YCAV0357E Chiller System Fault: HIGH DISCHARGE PRESSURE?
    • R
      Ronald SchultzAug 26, 2025
      A 'System Fault: HIGH DISCHARGE PRESSURE' in your York Chiller can arise from two primary causes. The coils might be dirty, so you should check and clean them. Alternatively, the system could be overcharged, necessitating the removal of charge and a check of subcooling.
  • J
    Jason MacdonaldAug 27, 2025
    How to resolve York Chiller Fault: HIGH AMBIENT TEMPERATURE?
    • H
      Heather NortonAug 28, 2025
      If your York Chiller is showing a 'Chiller Fault: HIGH AMBIENT TEMPERATURE', this could be due to two reasons: the ambient temperature is above the maximum operating limit, so check the outside air temperature. Alternatively, the ambient sensor could be defective, so check the panel display against a thermometer reading of the ambient temperature at the sensor.
  • R
    Richard KennedyAug 29, 2025
    How to fix York YCAV0357E Chiller Fault: LOW AMBIENT TEMPERATURE?
    • D
      Debbie HaleyAug 29, 2025
      If your York Chiller displays a 'Chiller Fault: LOW AMBIENT TEMPERATURE', it could be because the ambient temperature is lower than the programmed operating limit. Check the programmed cutout to determine if it is programmed correctly. It could also be that the ambient sensor is defective. Check the panel against the thermometer reading of ambient temperature.
  • S
    Stacy WestAug 31, 2025
    What causes York YCAV0357E Chiller System Fault: HIGH DISCHARGE TEMPERATURE?
    • W
      waynereidAug 31, 2025
      A 'System Fault: HIGH DISCHARGE TEMPERATURE' on your York Chiller could be caused by a defective discharge temperature sensor, so check the sensor. Another possible cause is high superheat, so measure the superheat with gauges and a thermocouple to determine the root cause.
  • A
    Anthony HarrisSep 2, 2025
    How to troubleshoot York Chiller when line fuse blows?
    • A
      Allison AllisonSep 2, 2025
      If the line fuse in your York Chiller keeps blowing, it could indicate a problem with several components. The SCR diode module might be defective, so check it. Alternatively, the IGBT module could be defective, so check that as well. Other potential causes include a defective VSD logic board (replace it if necessary) or a defective SCR trigger board (also replace if needed).
  • K
    Kristin PerkinsSep 4, 2025
    What does York Chiller System Fault: MOTOR CURRENT LIMITING mean?
    • V
      Valerie BondSep 4, 2025
      A 'System Fault: MOTOR CURRENT LIMITING' on your York Chiller indicates that high motor current has activated the current limiting feature. This can be a normal response from the controller if the ambient temperature is high.
  • A
    Annette WeaverSep 6, 2025
    What to do if York YCAV0357E shows System Fault: HIGH MOTOR TEMPERATURE?
    • D
      Dr. Sylvia PattersonSep 7, 2025
      If your York Chiller displays a 'System Fault: HIGH MOTOR TEMPERATURE', it suggests high motor temperature input from one of the sensors. This can be caused by low refrigerant charge, so check the subcooling.

Summary

General Chiller Information & Safety

Product Description

Variable Speed Drive (VSD) System

Explains the VSD's components, operation, cooling loop, and power section.

Rigging, Handling, and Storage

Rigging and Lifting Instructions

General procedures for rigging, handling, and lifting the chiller unit safely.

Installation

Electrical Connection

Recommendations for safe and satisfactory electrical connection of the unit.

Commissioning

First Time Start-Up

Guidance on initial start-up procedures, including heat load requirements and checklists.

Technical Data

Electrical Data - Wiring Diagrams

Power wiring diagrams and illustrations for electrical connections of 3 and 4 compressor units.

Operation

Operating Controls

Details on controls like Anti-recycle Timer, Evaporator Pump Control, and Unit Switch.

Basic Operating Sequence

Step-by-step process for initiating chiller start-up and loading.

Load Limiting Control

How load limiting prevents safety trips for parameters like motor current and pressure.

Micro Panel

VSD Operation and Controls

Details on VSD logic board, PWM generator, start/run sequences, and operating parameters.

VSD Safeties (Faults)

Explanation of various safeties and fault conditions related to the VSD.