York YCAV0457P - User Manual

York YCAV0457P
350 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
MODELS YCAV0267-0527, 60 HZ
STYLE A
(290-515 TONS)
AIR-COOLED SCREW LIQUID CHILLERS
E/V HIGH EFFICIENCY AND S/P STANDARD EFFICIENCY
50075
AIR-COOLED SCREW
LIQUID CHILLERS
INSTALLATION, OPERATION, MAINTENANCE Supersedes 201.21-NM3 (315) Form 201.21-NM3 (616)
035-20994-000
R134a
Issue Date:
June 30, 2016

Table of Contents

Questions and Answers

  • D
    daviselizabethAug 20, 2025
    What to do if York YCAV0457P has System Fault: LOW SUCTION PRESSURE?
    • J
      Jill NicholsAug 20, 2025
      If your York Chiller is showing a 'System Fault: LOW SUCTION PRESSURE', there are a couple of potential causes. It could be due to a low charge, in which case you should check the subcooling. Alternatively, the transducer might be reading incorrectly; compare its reading against a gauge.
  • B
    benjaminbriggsAug 22, 2025
    Why York Chiller has no display on control panel and won't run?
    • M
      Monica DuncanAug 22, 2025
      If your York Chiller's control panel has no display and the unit won't run, the issue might stem from several causes: * The high voltage supply to the chiller could be missing. * A line fuse may be blown, so check the fuses. * The chiller control board could be defective, requiring replacement. * The display board itself might be defective, also requiring replacement.
  • S
    Scott WatsonAug 25, 2025
    What to do if my York YCAV0457P Chiller shows System Fault: HIGH OIL TEMPERATURE?
    • M
      Mary BrownAug 25, 2025
      If your York Chiller displays a 'System Fault: HIGH OIL TEMPERATURE' message, it could be due to several reasons. First, the oil temperature sensor might be defective; you can check it with infrared to see if the reading is reasonable. Second, the condenser fans might not be operating or are running backward, so check the fans. Lastly, the coils could be dirty; inspect and clean them if necessary.
  • S
    Scott BellAug 26, 2025
    What causes York YCAV0457P System Fault: HIGH DISCHARGE PRESSURE?
    • M
      Melissa RiceAug 26, 2025
      A 'System Fault: HIGH DISCHARGE PRESSURE' in your York Chiller can arise from two primary causes. The coils might be dirty, so you should check and clean them. Alternatively, the system could be overcharged, necessitating the removal of charge and a check of subcooling.
  • E
    Elizabeth HoltAug 28, 2025
    How to resolve York Chiller Fault: HIGH AMBIENT TEMPERATURE?
    • J
      julie40Aug 28, 2025
      If your York Chiller is showing a 'Chiller Fault: HIGH AMBIENT TEMPERATURE', this could be due to two reasons: the ambient temperature is above the maximum operating limit, so check the outside air temperature. Alternatively, the ambient sensor could be defective, so check the panel display against a thermometer reading of the ambient temperature at the sensor.
  • L
    Luis MartinezAug 29, 2025
    How to fix York Chiller Fault: LOW AMBIENT TEMPERATURE?
    • G
      Gerald HuertaAug 30, 2025
      If your York Chiller displays a 'Chiller Fault: LOW AMBIENT TEMPERATURE', it could be because the ambient temperature is lower than the programmed operating limit. Check the programmed cutout to determine if it is programmed correctly. It could also be that the ambient sensor is defective. Check the panel against the thermometer reading of ambient temperature.
  • K
    kellynelsonSep 1, 2025
    What causes York YCAV0457P System Fault: HIGH DISCHARGE TEMPERATURE?
    • M
      Matthew BlackSep 1, 2025
      A 'System Fault: HIGH DISCHARGE TEMPERATURE' on your York Chiller could be caused by a defective discharge temperature sensor, so check the sensor. Another possible cause is high superheat, so measure the superheat with gauges and a thermocouple to determine the root cause.
  • M
    Matthew OchoaSep 2, 2025
    How to troubleshoot York Chiller when line fuse blows?
    • J
      John WalkerSep 3, 2025
      If the line fuse in your York Chiller keeps blowing, it could indicate a problem with several components. The SCR diode module might be defective, so check it. Alternatively, the IGBT module could be defective, so check that as well. Other potential causes include a defective VSD logic board (replace it if necessary) or a defective SCR trigger board (also replace if needed).
  • A
    alvarezlaurenSep 5, 2025
    What does York YCAV0457P Chiller System Fault: MOTOR CURRENT LIMITING mean?
    • S
      Stacy RuizSep 5, 2025
      A 'System Fault: MOTOR CURRENT LIMITING' on your York Chiller indicates that high motor current has activated the current limiting feature. This can be a normal response from the controller if the ambient temperature is high.
  • A
    Austin SantosSep 6, 2025
    What to do if York YCAV0457P Chiller shows System Fault: HIGH MOTOR TEMPERATURE?
    • S
      Seth CookSep 7, 2025
      If your York Chiller displays a 'System Fault: HIGH MOTOR TEMPERATURE', it suggests high motor temperature input from one of the sensors. This can be caused by low refrigerant charge, so check the subcooling.

York YCAV0457P Specifications

General IconGeneral
BrandYork
ModelYCAV0457P
CategoryChiller
LanguageEnglish