What to do if York YCAV0527P Chiller has System Fault: LOW SUCTION PRESSURE?
- CChristopher WhiteAug 20, 2025
If your York Chiller is showing a 'System Fault: LOW SUCTION PRESSURE', there are a couple of potential causes. It could be due to a low charge, in which case you should check the subcooling. Alternatively, the transducer might be reading incorrectly; compare its reading against a gauge.