EasyManua.ls Logo

York YCH120 - General Information

York YCH120
99 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FORM 150.40-NM20
3
YORK INTERNATIONAL
GENERAL INFORMATION
GENERAL DESCRIPTION
The YCHA packaged liquid chillers are completely self-
contained outdoor units shipped ready for final job
installation requiring only liquid connections, power and
control wiring. They are designed primarily for central
station air conditioning applications with normal instal-
lations being on roof-tops or on ground level beside the
building.
CODE STATUS
The units are designed in accordance with N.E.C., ANSI
B9.1, and ASME Codes.
OPERATING LIMITATIONS
LEAVING LIQUID MIN. 40
TEMP., °F MAX. 50
AIR ON MIN. 35*
CONDENSER, °F MAX. 130
UNIT COOLER
MODEL
WATER GPM
YCHA MIN. MAX.
100 120 550
120 120 580
150 120 580
175 150 640
200 200 700
* 0°F With Optional Low Ambient Kit.
NOTE: The evaporator is protected against freeze-up to - 20°F with
an electrical heater cable.
COMPRESSOR NOMENCLATURE
Compressor Series
Single Stage
No. of Active Cylinders
(4,6,&8)
Stroke (3, 4)
Design Level (E)
Motor Size (M,N,Q,P,S,T)
Voltage Code:
17= 200-3-60
28 = 230-3-60
40 = 380-3-60
46 = 460-3-60
50 = 380/415-3-50
64 = 346-3-50
Motor Manufacturer
(A = A.O. Smith, G = G.E.)
J S 4 3 E M -17 G
TABLE 1 VOLTAGE LIMITATIONS
LD01773
FIG. 1 COOLER WATER PRESSURE DROP
VOLTAGE OPTIMUM MIN. MAX.
CODE VOLTAGES VOLTS VOLTS
17 200-3-60 180 220
28 230-3-60 207 253
40 380-3-60 355 415
46 460-3-60 414 506
50 380/415-3-50 342 440
64 346-3-50 311 381

Related product manuals