1034350-UCL-D-0817
Unitary Products Group 5
OPERATING MEASUREMENTS - COOLING
REFRIGERANT SAFETIES
OPERATING MEASUREMENTS ELECTRIC HEATING
Heater kW ____________kW Heater Voltage, Nameplate ____________ Volts
Heater Model Number: _______________________________
Serial Number: ______________________________________
Stage
Discharge
Pressure
Discharge
Temp.
Liquid Line
Pressure At
Service
Valve
Liquid Line
Temp.
1
1. Liquid line temperature should be taken before filter/drier.
Subcooling
2
2. Subtract 10 psi from discharge pressure for estimated liquid line pressure
Suction
Pressure
Suction
Temp.
Superheat
First
3
3. If Rawal valve installed, contact Technical Service.
#°# ° °#°°
Second (if equipped) # ° # ° ° # ° °
Third (if equipped) # ° # ° ° # ° °
Fourth (if equipped) # ° # ° ° # ° °
Heat Pump 1st Stage # ° # ° ° # ° °
Outside air temperature ________________ db °F ________________ wb °F ________________ RH%
Return Air Temperature ________________ db °F ________________ wb °F ________________ RH%
Mixed Air Temperature ________________ db °F ________________ wb °F ________________ RH%
Supply Air Temperature ________________ db °F ________________ wb °F ________________ RH%
Action Completed See Notes
Prove Compressor Rotation (3 phase only) by guage pressure
Prove High Pressure Safety, All Systems
Prove Low Pressure Safety, All Systems
Heater Nameplate Measured List All Three Amperages
Stage 1 _________AMPS _________AMPS _________AMPS _________AMPS
Stage 2 _________AMPS _________AMPS _________AMPS _________AMPS
Stage 3 _________AMPS _________AMPS _________AMPS _________AMPS
Stage 4 _________AMPS _________AMPS _________AMPS _________AMPS
Checked Heater Limit Yes
No
Air Moving Switch Installed? Yes
No