Parameters relating to defrost
Parameters relating to defrost
Parameters Description Level VS Unit Max. Min. Value
d01
Defrost operation:
0= Absent (function not available)
1= Present
U 7 (R/W) - 1 0 1
d02
Defrost at time or temperature:
0= Time (function not available)
1= Temperature / Pressure
U 8 (R/W) - 1 0 1
d03 Defrost start pressure U 19 (R/W) bar d04 /11 5,8
d04 Defrost end pressure U 21 (R/W) bar /12 d03 26
d05 Minimum defrost start time U 37 (R/W) Seconds 150 10 10
d06 Minimum defrost duration U 38 (R/W) Seconds 150 0 0
d07 Maximum defrost duration U 39 (R/W) Minutes 15 1 10
d08 Time between two defrost cycles U 40 (R/W) Minutes 150 10 30
d11
Activation of heaters during defrost:
0= No
1= Yes
U 9 (R/W) - 0 1 1
d12 Compressor stoppage before defrost F 43 (R/W) Minutes 3 0 0
d13 Compressor stoppage after defrost F 44 (R/W) Minutes 3 0 0
d16
Forced ventilation time at defrost end (if
F13=2 only)
F 47 (R/W) Minutes 360 0 0
d17 Defrost with compressor off F 22 (R/W) °C 80 0 0
A
Defrost end tempera‐
ture (d04)
E
Minimum defrost start time
(d05)
B Defrost start F Timer start
C Defrost end G
Defrost start temperature
(d03)
D
Maximum defrost du‐
ration (d06)
A
B
C
D
E
F
G