44 JOHNSON CONTROLS
FORM 150.63-EG4 (1012)
NOITPIRCSEDnoitangiseDNOITPIRCSEDnoitangiseD
ACC A CCESSORY -QCB CIRCUIT BREAKER
- ADIS DISPLAY BOARD
-QMMSC
MA NUA L MOTOR STARTER COMPRESSOR
PMUP RETRATS ROTOM LAUNAMPSMMQ-DRAOB ORCIMBMA -
-QSD SWITCH DISCONNECT
- BAMB AMBIENT
-BDAT DISCHA RGE A IR TEMPERA TURE
R RESISTOR
DERDER ERUSSERP EGRAHCSIDPDB -
- BECT ENTERING CHILLED TEMPERATURE RP RUN PERMISSIV E
- BLCT LEAVING CHILLED TEMPERATURE RU REMOTE UNLOAD Ist STEP
NOT FITTED ON REM
OTE EVAP. UNITS
SCH THERMOSTAT CRANKCASE HEATER
-BMP MOTOR PROTECTOR COMPRESSOR SCR SCREEN
HCTIWS WOLFFS -ERUSSERP NOITCUSPSB -
- SKP KEYPAD
-CPF CAPACITOR POWER FACTOR - SOA SWITCH OFF A UTO
-SZT ZONE THERMOSTAT
- ECH CRA NKCASE HEATER
-EEH EVA PORATOR HEA TER
- T TRANSFORMER
TNERRUC REMROFSNARTCT-RETAEH YREVOCER TAEHHRHE-
-EPH PUMP HEATER
-EXT EXTERNAL TO CONTROL PA NEL -UBR BRIDGE RECTIFIER
- F FUSE -WHT WHITE
PX- TUOTUC ERUSSERP HG
IHPHF -
PLUGS BETWEEN POW./MICRO. SECTION
-FSC FAN SPEED CONTROLLER
- XTBC TERMINA L BLOCK CUSTOMER
FAN SPEED INHIBIT TWO SPEED - XTBF TERMINA L BLOCK FACTORY
FAN OPTION ONLY
-Y ESV EV APORATOR SOLENOID VALVE
GND GROUND
-Y HGSV HOT GAS SOLENOID VALVE
G/Y GREEN / YELLOW
(INCLUDING COIL SUPPRESSOR)
LIQUID LINE SOLENOID VALVE
ER NO DERIW DNA DETNUOM DLEIFROTCENNOC DRAOB GULP J MOTE
EV AP. UNIT
ROSSERPMOCRPCZ -YALER DRAOB TIUCRICK-
-KF
(
INCLUDING COIL SUPPRESSOR)
-KFH
FAN CONTACTOR HIGH SPEED
(INCLUDING COIL SUPPRESSOR)
-KFL
FAN CONTACTOR LOW SPEED
NOTE WELL {SEE NOTE}
(INCLUDING COIL SUPPRESSOR)
-KFOL FAN OVERLOAD
-KFS RELA Y FAN SPEED WIRING AND ITEMS SHOWN THUS
-KH HEATER RELAY
ARE STANDARD Y ORK ACCESSORIES
-KM COMPRESSOR CONTA CTOR
(INCLUDING COIL SUPPRESSOR)
WIRING AND ITEMS SHOWN THUS
-KCR CONTROL RELAY ARE NOT SUPPLIED BY Y ORK
-KP PUMP CONTACTOR PA RT
(INCLUDING COIL SUPPRESSOR)
ITEMS THUS ENCLOSED FORM A
-KT RELA Y TIMER COMPONENTS OR SETS OFCOMPONENTS
- M COMPRESSOR MOTOR
-MF MOTOR FA N
-MP MOTOR PUMP
NU NOT USED
PE PROTECTIV E EARTH
PWM PULSE WIDTH MODULATION TEMP
RESET or REMOTE UNLOAD 2nd STEP
- Y LLSV
-FSI
NB
GENERAL
a. THIS DRAWING IS BASED ON IEC SYMBOLS.
b.
FIELD WIRING TO BE IN ACCORDANCE WITH THE RELEVANT ELECTRICAL CODE AS WELL AS ALL OTHER
APPLICABLE CODES AND SPECIFICATIONS
c. ALL SOURCES OF SUPPLY SHOWN ON THIS DIAGRAM TO BE TAKEN FROM ONE MAIN ISOLATOR, NOT
SHOWN OR SUPPLIED BY YORK.
d. GREEN AND YELLOW WIRE IS USED FOR EARTH, MULTI-COLOURED CABLE USED FOR LOW VOLTAGE.
RED WIRE USED FOR A.C. CONTROL, BLUE WIRE FOR NEUTRAL, BL
ACK WIRE FOR A.C. AND D.C.
POWER. ORANGE WIRE SHOULD BE USED FOR INTERLOCK CONTROL WIRING SUPPLIED BY EXTERNAL
SOURCE.
e. LEGEND DESIGNATION DEPICTS COMPONENT ABBREVIATIONS. NUMBER PREFIX LOCATED, IF
APPLICABLE, ON SCHEMATIC CIRCUIT, REFERS TO SYSTEM THEREON, E.G.= 1-FHP2 REFERS TO HIGH
PRESSURE CUTOUT NO 2 ON SYSTEM NO 1.
f. ALL WIRING TO CONTROL SECTION VOLTAGE FREE CONTACTS REQUIRES A SUPPLY PROVIDED BY THE
DERIVING THE SUPPLIES
FOR THE VOLTAGE FREE TERMINALS WITH REGARD TO A COMMON POINT OF
ISOLATION. THUS, THESE CIRCUITS WHEN USED MUST BE FED VIA THE COMMON POINT OF ISOLATION
THE VOLTAGE TO THESE CIRCUITS IS REMOVED WHEN THE COMMON POINT OF ISOLATION TO THE UNIT
IS OPENED. THIS COMMON POINT OF ISOLATION IS NOT SUPPLIED BY YORK. THE YORK VOLTAGE
FREE CONTACTS ARE RATED AT 100VA. ALL INDUCTIVE DEVICES {RELAYS} SWITCH BY THE YORK
VOLTAGE FREE CONT
ACTS MUST HAVE THEIR COIL SUPPRESSED USING STANDARD R/C SUPPRESSORS.
g. CUSTOMER VOLTAGE FREE CONTACTS CONNECTED TO TERMINAL 13 MUST BE RATED AT 30V 5ma
NO CONTROLS {RELAYS ETC.} SHOULD BE MOUNTED IN ANY SECTION OF THE CONTROL PANEL.
ADDITIONALLY, CONTROL WIRING NOT CONNECTED TO THE YORK CONTROL PANEL SHOULD NOT BE RUN
THROUGH THE PANEL.
IF THESE PRECAUTIONS ARE NOT FOLLOWED, ELECTRICAL NOISE COULD CAUSE MALFUNCTIONS OR
DAMAG
E TO THE UNIT AND ITS CONTROLS.
I. 120/14.3 - (SIGNAL IN/OUT) I.E. 120 IS WIRE # AND 14.3 REFERS TO SHT. 14 COLUMN 3
h.
NOTES
1
REFER TO INSTALLATION COMMISIONING OPERATION AND MAINTENANCE MANUAL FOR CUSTOMER
CONNECTIONS AND CUSTOMER CONNECTION NOTES, NON COMPLIANCE TO THESE INSTRUCTIONS WILL
INVALIDATE UNIT WARRANTY.
2
WIRING AND COMPONENTS FOR COMPRESSOR 3 ONLY FITTED WHEN UNIT HAS 3 COMPRESSORS ON
THE SYSTEM. 1-BMP3 IS REPLACED BY A LINK ACROSS TERMINALS 134 & 135. 2-BMP3 IS REPLACED BY A
LINK ACROSS TERMINALS 234 & 235.
3
FHP2 IS ONLY FITTED ON CE YLAA0180 AND ABOVE. WHEN NOT FITTED 1-FHP2 IS REPLACED BY A LINK
ACROSS TERMINALS 132 & 139. 2-FHP2 IS REPLACED BY A LINK ACROSS TERMINALS 232 & 239
4 FITTED ON UNITS WITH HOT GAS BYPASS OPTION.
5 EMS OPTION IS WIRED AS SHOWN
6 THIS WIRING MUST BE USED FOR OLD DISPLAY 031-0110-000
7 NETWORK CONNECTION POINT
8 PRINTER PORT
9 REMOTE EMERGENCY STOP CAN BE WIRED BETWEEN TERMIN
AL L AND 5 AFTER REMOVING LINK
10
POWER FACTOR CORRECTION ACCESSORY. POWER FACTOR CORRECTION FITTED TO EACH
COMPRESSOR CONTACTOR
11
NOT FITTED ON COMPRESSORS WITH INTERNAL MOTOR PROTECTION. FOR SYSTEM 1 TERMINALS 132 &
133, 133 & 134 AND 134 & 135 ARE LINKED. FOR SYSTEM 2 TERMINALS 232 & 233, 233 & 234 AND 234 & 235
ARE LINKED.
12 ONLY FITTED ON SYSTEMS WITH 3 OR 4 FANS
13 ONLY FITTED ON SYSTEMS WITH 4 FANS
14 ONLY FITTED ON SYSTEMS WI
TH 5 FANS
15 ONLY FITTED ON SYSTEMS WITH 6 FANS
16
INPUT SWITCH DISCONNECT ( STANDARD ON CE UNITS) OR CIRCUIT BREAKER OPTION REPLACES
INPUT TERMINAL BLOCK
17
INPUT SWITCH DISCONNECT & INDIVIDUAL SYSTEM CIRCUIT BREAKER OPTION REPLACES INPUT
TERMINAL BLOCK
18
115V CONTROL CIRCUIT REQUIRES A 115V SUPPLY UNLESS CONTROL CIRCUIT TRANSFORMER
-T2 & -F3 ARE FITTED (STANDARD ON CE UNITS)
19
FOR OPTIONAL HYDRO KIT. HEATER -EPH IS FITTED
AND WIRED AS SHOWN.
ON SINGLE PUMP -KP1, -QMMSP1 & -MP1 ARE FITTED & WIRED AS SHOWN.
ON TWO PUMP HYDRO KITS -KP2, -QMMSP2 & -MP2 ARE ALSO FITTED AND WIRED AS SHOWN.
20 CURRENT MEASUREMENT OPTION WIRED AS SHOW
21 ONLY FITTED ON SYSTEMS WITH SINGLE SPEED FANS
22 ONLY FITTED ON SYSTEMS WITH TWO SPEED FANS
23 OPTIONAL COMPRESSOR MANUAL MOTORS STARTERS ( STANDARD ON CE UNITS)
24 SEE SHEET 3 OF CONNECTION DIAGRAM FOR POWER INPUT OP
TIONS
25 ALTERNATE CONNECTIONS SHOWN FOR DIFFERENT TWO SPEED MOTOR TYPES
26 ONLY FITTED ON SYSTEMS WITH A MAXIMUM OF 4 FANS
27 220/230V UNITS REQUIRE A SEPARATE FUSE FOR UNITS W/4 OR MORE FANS PER SYSTEM
28 LOW AMBIENT KIT -FSC FOR FAN -MF1 IS ONLY FITTED ON SYSTEMS WITH LESS THAN 4 FANS
29 ONLY FITTED ON YLAA0091
30 ONLY FITTED ON YLAA0090,0091, 0135
31 INPUT DUAL POINT CIRCUIT BREAKER OPTION REPLACES INPUT TERMINAL BLOCK
32 FIELD INS
TALLED ON REMOTE EVAPORATOR UNITS
33 FITTED ON UNITS WITH SINGLE PHASE MOTORS ONLY
34 FITTED ON UNITS WITH LOW AMBIENT OPTION ONLY
35 ONLY FITTED ON UNITS WITH AN ACOUSTIC KIT
36 ONLY FITTED ON HEAT RECOVERY UNITS
37 ONLY FITTED ON CONDENSING UNITS
38 OMITTED ON CONDENSING UNITS
Electrical Drawings - continued