036-21570-002 Rev. D (0605)
20 Unitary Products Group
Multipliers for determining the performance with other indoor sections.
HEATING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO. YMA04211
INDOOR COIL MODEL NO. G2FD048S21
AIR TEMP.
ENTERING
OUTDOOR
UNIT
AIR TEMP.
ENTERING
INDOOR
COIL
ID CFM
1200 1400 1600
MBTUH KW C.O.P. MBTUH KW C.O.P. MBTUH KW C.O.P.
60
60 49.8 3.6 4.1 50.8 3.4 4.4 51.9 3.3 4.6
70 47.2 3.9 3.6 48.2 3.7 3.8 49.2 3.6 4.0
80 44.7 4.2 3.1 45.7 4.1 3.3 46.6 3.9 3.5
47
60 43.7 3.3 3.9 44.5 3.2 4.1 45.3 3.1 4.3
70 41.3 3.6 3.3 42.0 3.5 3.5 42.7 3.4 3.7
80 38.9 4.0 2.9 39.5 3.8 3.0 40.1 3.7 3.2
40
60 40.0 3.2 3.7 40.8 3.1 3.8 41.5 3.0 4.0
70 37.9 3.5 3.1 38.5 3.4 3.3 39.1 3.3 3.4
80 35.8 3.8 2.7 36.2 3.7 2.8 36.6 3.6 3.0
30
60 36.0 3.1 3.4 36.5 3.0 3.6 37.1 2.9 3.7
70 33.9 3.4 2.9 34.3 3.3 3.1 34.7 3.2 3.2
80 31.8 3.7 2.5 32.1 3.6 2.6 32.4 3.5 2.7
17
60 28.5 3.2 2.6 28.9 3.1 2.7 29.3 3.1 2.8
70 27.6 3.4 2.4 28.0 3.3 2.5 28.4 3.2 2.6
80 26.8 3.5 2.2 27.1 3.4 2.3 27.4 3.4 2.4
10
60 27.9 2.8 2.9 28.5 2.8 3.0 29.1 2.7 3.1
70 26.0 3.1 2.4 26.4 3.1 2.5 26.8 3.0 2.6
80 24.1 3.4 2.1 24.3 3.4 2.1 24.5 3.3 2.2
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler Coil
MBH KW COP
F2FP048 0.99 0.99 1.00
N1VSC16 G2FD048(S,H)21(T) 0.98 1.04 0.94
N1VSD20 G2FD048(S,H)24(T) 0.98 1.05 0.93
N1AHC16 G2FD048(S,H)21(T) 1.00 1.00 1.00
N1AHD20 G2FD048(S,H)24(T) 1.00 1.00 1.00
G1FA048S21 1.00 1.00 1.00
G2FD048(S,H)21,24 1.00 1.00 1.00
G1NA060S24T 1.01 1.02 0.99
G1HD048 0.99 0.99 0.99
G1HA048H21 0.99 1.00 0.99
Variable Speed
Furnace
Coil
T.C. S.C. KW
P*DUC20V G1FA048S21 0.99 1.03 0.96
P*DUC20V G2FD048(S,H)21(T) 1.00 1.05 0.95
P1XUC16V G1FA048S21 0.99 1.03 0.96
P1XUC16V G2FD048(S,H)21(T) 1.00 1.05 0.96
P1XUC20V G1FA048S21 0.99 1.02 0.97
P1XUC20V G2FD048(S,H)21(T) 1.00 1.04 0.96
P1XDD20V G2FD048(S,H)24(T) 1.00 1.02 0.98
P1XDC20V G2FD048(S,H)21(T) 1.00 1.01 0.99
P1XDC20V G1HA048H21 0.99 1.00 0.99