01987654321noitpircseD tsiL tnioPISlairepmI
33 S2_HI_MTR_T AI25 538 03,04 x10 ADF 29 °F °C Sys 2 Highest SSerutarepmeT rotoM
34 VSD_OUT_FR AI26 539 03,04 x10 ADF 30 Hz Hz VSD Output Frequency S S
35 VSD_CMD_FR AI27 540 03,04 x10 ADF 31 Hz Hz VSD Command Fr SSycneuqe
36 S1_COND_DR AI28 541 03,04 x10 ADF 32 % % Sys 1 Condenser Drain Valve % Open S S
37 S2_COND_DR AI29 542 03,04 x10 ADF 33 % % Sys 2 Condenser Drain Valve % Open S S
38 S1_OP_CODE AI30 543 03,04 x1 ADF 34 None None Sys 1 Operational Code S S
39 S2_OP_CODE AI31 54
4 03,04 x1 ADF 35 None None Sys 2 Operational Code S S
40 S1_FTL_CODE AI32 545 03,04 x1 ADF 36 None None Sys 1 Fault Code S S
41 S2_FLT_CODE AI33 546 03,04 x1 ADF 37 None None Sys 2 Fault Code S S
42 S1_FAN_STG AI34 547 03,04 x1 ADF 38 None None Sys 1 Conde SS]41-0[ egatS naF resn
43 S2_FAN_STG AI35 548 03,04 x1 ADF 39 None None Sys 2 Conde SS]41-0[ egatS naF resn
44 S1_FAN_SPD AI36 549 03,04 x10 ADF 40 % % Sys 1 Condenser OO)DSV( deepS naF
45 S2_FAN_SPD AI37 550 03,04 x10 ADF 41 % % Sys 2 Condenser OO)DSV( deepS naF
46 LEAD AI38 551 03,
04 x1 ADF 42 None None Lead System S S
47 LCHLT_SETP AI39 552 03,04 x10 ADF 43 °F °C Leaving Chille SStniopteS diuqiL d
48 LCHLT_CUTOUT AI40 553 03,04 x10 ADF 44 °F °C Leaving Chil SStuotuC diuqiL del
49 S1_ECON_VLV AI41 554 03,04 x10 ADF 45 % % Sys 1 Economize SSnepO % evlaV r
50 S2_ECON_VLV AI42 555 03,04 x10 ADF 46 % % Sys 2 Economize SSnepO % evlaV r
51 SUCT_PRS_CUT AI43 556 03,04 x10 ADF 47 PSI BAR Suction Pr SStuotuC erusse
52 VSD_DCB_VT AI44 557 03,04 x1 ADF 48 Volts Volts
VSD DC Bus Voltage (Unit)
VSD DC Bus Voltage Sys
1 (Frame E/F)
S S
53 VSD_DCB_VT2 AI45 558 03,04 x1 ADF 49 Volts Volts VSD DC Bus Voltage Sys 2 (Frame E/F) O O
54 REM_SETPOINT AI46 559 03,04 x10 ADF 50 °F °C Remote Leaving Chilled Liquid Setpoint S S
55 S1_SUBCOOL AI47 560 03,04 x10 ADF 51 °F (diff) °C (diff) OO)lennahcorciM( gniloocbuS 1 syS
56 S1_EVAP_LL AI48 561 03,04 x10 ADF 52 % % Sys 1 Evaporator Liquid Level (Round Tube) S S
57 S2_SUBCOOL AI49 562 03,04 x10 ADF 53 °F (diff) °C (diff) OO)lennahcorciM( gniloocbuS 2 syS
58 S2_EVAP_LL AI50 563 03,04 x10 ADF 54 % % Sys 2
Evaporator Liquid Level (Round Tube) S S
59 COOLING_RNG AI51 564 03,04 x10 ADF 55 °F °C Cooling Range S S
60 S1_DSC_SHEAT AI52 565 03,04 x10 ADF 56 °F (diff) °C (dif SStaehrepuS egrahcsiD 1 syS)f
61 S2_DSC_SHEAT AI53 566 03,04 x10 ADF 57 °F (diff) °C (dif SStaehrepuS egrahcsiD 2 syS)f
62 S1_SYS_STATE AI54 567 03,04 x1 ADF 58 None None
Sys 1 System State [0=Stopped, 1=Running, 2=Faulted,
4=Locked Out, 5=Pre-Run
S S
63 S2_SYS_STATE AI55 568 03,04 x1 ADF 59 None None
Sys 2 System State [0=Stopped, 1=Running, 2=Faulted,
4=Lo
cked Out, 5=Pre-Run
S S
64 S1_MTR_OVER AI56 569 03,04 x1 ADF 60 Amps Amps Sys 1 Moto SSgnitteS daolrevO tnerruC r
65 S2_MTR_OVER AI57 570 03,04 x1 ADF 61 Amps Amps Sys 2 Moto SSgnitteS daolrevO tnerruC r
66 FAN_TYPE AI58 571 03,04 x1 ADF 62 None None Condenser Fan SS]4-1[ epyT lortnoC
67 FC_MODE AI59 572 03,04 x1 ADF 63 None None
Free Cooling Mode [0=Mech, 1=Free Cool, 2=Hybrid]
(Free Cooling)
O O
68 FC_CTRL AI60 573 03,04 x1 ADF 64 % %
Free Cooling Control Programmed [0=Disabled, 1=Open
Loop, 2=Closed Loop] (Free Cooling)
N O
69
CC_BYP_VALVE AI61 574 03,04 x10 ADF 65 % % Cooling Coil Bypass Valve (Free Cooling Closed Loop) N O
70 CC_VALVE AI62 575 03,04 x10 ADF 66 % % Cooling Coil Valve (Free Cooling Closed Loop) N O
71 CC_TEMP AI63 576 03,04 x10 ADF 67 °F °C Cooling Coil Temperature (Free Cooling Closed Loop) N O
72 HX_LEAVE_TEMP AI64 577 03,04 x10 ADF 68 °F °C
Heat Exchanger Leaving Temperature (Free Cooling
Closed Loop)
N O
73