JOHNSON CONTROLS
146
SECTION 8 - MICROPANEL
FORM 201.28-NM1.1
ISSUE DATE: 1/31/2018
TABLE 24 - SETPOINT LIMITS
PROGRAM VALUE MODE LOW LIMIT HIGH LIMIT DEFAULT
Leaving Chilled Liquid Setpoint
Water Cooling
40.0°F 60.0°F 44.0°F
4.4°C 15.6°C 6.7°C
Glycol Cooling
15.0°F 70.0°F 44.0°F
-9.4°C 15.6°C 6.7°C
Leaving Chilled Liquid Control Range -
1.5°F 2.5°F 2.0°F
0.8°C 1.4°C 1.1°C
Max. Remote Temperature Reset -
2°F 40°F 20°F
1°C 22°C 11°C
The â–² (ARROW) key allows scrolling back through
the setpoints displays.
The minimum, maximum, and default values
allowed under the SETPOINTS key are provided in
Table 24 on page 146.