JOHNSON CONTROLS
74
SECTION 5 - TECHNICAL DATA
FORM 201.28-NM1.1
ISSUE DATE: 1/31/2018
ALL DIMENSIONS - INCHES (MM)
YVAA
A B C D
E-NOZZLE
SIZE
F G
WATER
VOLUME
GALLONS
(LITERS)
MINIMUM
CHILLED
WATER
FLOW RATE
GPM (L/S)
MAXIMUM
CHILLED
WATER
FLOW RATE
GPM (L/S)
FRAME
COND.
15 3
15.1
(384)
11.4
(290)
6.8
(173)
– 6
34.5
(876)
–
58
(220)
250
(16)
980
(62)
16 5
15.1
(384)
11.4
(290)
29.4
(747)
– 6
56.1
(1425)
–
58
(220)
250
(16)
980
(62)
17 8
15.1
(384)
11.4
(290)
34.9
(886)
– 6
70
(1778)
–
71
(269)
300
(19)
1170
(74)
18 3
14.1
(358)
11.4
(290)
17.7
(450)
– 6
56.8
(1443)
–
48
(182)
200
(13)
790
(50)
19 5
14.1
(358)
11.4
(290)
61.5
(1562)
– 6
56.7
(1440)
–
48
(182)
200
(13)
790
(50)
19 8
15.3
(389)
11.4
(290)
117.3
(2979)
– 6
56.1
(1425)
–
58
(220)
250
(16)
980
(62)
20 0
15.1
(384)
11.4
(290)
1.7
(43)
– 6
38.1
(968)
–
71
(269)
300
(19)
1170
(74)
21 3
14.1
(358)
11.4
(290)
61.7
(1567)
– 6
58.8
(1494)
–
48
(182)
200
(13)
790
(50)
21 5
15.1
(384)
11.4
(290)
29.9
(759)
– 6
70
(1778)
–
71
(269)
300
(19)
1170
(74)
21 8
15.3
(389)
11.4
(290)
78.9
(2004)
– 6
70.3
(1786)
–
71
(269)
300
(19)
1170
(74)
TABLE 8 - STANDARD TWO-PASS, REAR INLET/OUTLET EVAPORATOR
NOTE: Minimum Chilled Water Flow Rate is for full load selections; Variable Primary Flow ratings as low as 50% of the minimum are
permitted. Glycol limits are higher. Please contact your Johnson Controls Sales Ofce for ratings and further information.