EasyManua.ls Logo

York YVAA - Table 9 - Optional Three-Pass Inlet;Outlet Connections

York YVAA
178 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SECTION 5 - TECHNICAL DATA
JOHNSON CONTROLS
75
FORM 201.28-NM1.1
ISSUE DATE: 1/31/2018
5
ALL DIMENSIONS - INCHES (MM)
YVAA
A B C D
E-NOZZLE
SIZE
F G
WATER
VOLUME
GALLONS
(LITERS)
MINIMUM
CHILLED
WATER
FLOW RATE
GPM (L/S)
MAXIMUM
CHILLED
WATER
FLOW RATE
GPM (L/S)
FRAME
COND.
23 3
15.1
(384)
11.4
(290)
73.3
(1862)
– 6
56.1
(1425)
–
58
(220)
250 (16) 980 (62)
24 5
15.3
(389)
11.4
(290)
29.9
(759)
– 6
56.1
(1425)
–
71
(269)
300 (19) 1170 (74)
24 8
15.3
(389)
11.4
(290)
122.9
(3122)
– 6
70
(1778)
–
71
(269)
300 (19) 1170 (74)
26 3
15.3
(389)
11.4
(290)
117.3
(2979)
– 6
56.1
(1425)
–
58
(220)
250 (16) 980 (62)
27 0
15.3
(388)
11.4
(290)
16.8
(427)
– 6
51.9
(1318)
–
82
(310)
300 (19) 1170 (74)
27 3
15.3
(389)
11.4
(290)
42.9
(1090)
– 6
70
(1778)
–
82
(310)
300 (19) 1170 (74)
27 5
15.5
(394)
14
(356)
44.3
(1125)
– 8
71.8
(1824)
–
113
(428)
410 (26) 1600 (101)
27 8
15
(381)
14
(356)
88.3
(2243)
– 8
71.8
(1824)
–
113
(428)
410 (26) 1600 (101)
29 5
15.5
(394)
14
(356)
88.3
(2243)
– 8
71.8
(1824)
–
113
(428)
410 (26) 1600 (101)
30 3
15.3
(389)
11.4
(290)
122.9
(3122)
– 6
70
(1778)
–
71
(269)
300 (19) 1170 (74)
TABLE 8 - STANDARD TWO-PASS, REAR INLET/OUTLET EVAPORATOR (CONT'D)
NOTE: Minimum Chilled Water Flow Rate is for full load selections; Variable Primary Flow ratings as low as 50% of the minimum are
permitted. Glycol limits are higher. Please contact your Johnson Controls Sales Ofce for ratings and further information.

Table of Contents

Other manuals for York YVAA

Related product manuals