Item
1
2
3
4
5
6
7
8
9
10
01987654321noitpircseD tsiL tnioPISlairepmI
1 REM_SETP AV1 1026 03,06,16 Div 10 ADF 1 °F °C Remote Setpoint (Start cmd must be active to take effect) S S
2 DMD_LIMIT AV2 1027 03,06,16 Div 10 ADF 2 % FLA % FLA
Remote Current Limit Setpoint (Start cmd must be active
to take effect)
S S
3 SND_LIMIT AV3 1028 03,06,16 Div 10 ADF 3 % %
Remote Sound Limit (RSL option must be enabled or point
ignored)
S S
4 SPARE AV1 AV4 1029 03,06,16 Div 10 ADF 4 None None Spare N N
5 START_STOP BV1 1538 01,03,05,06,15 N/A BD 1 0/1 0/1 R
emote Start / Stop Command [0=Stop, 1=Run] S S
6 SPARE_BV1 BV2 1539 01,03,05,06,15 N/A BD 2 0/1 0/1 Spare N N
7 SPARE_BV2 BV3 1540 01,03,05,06,15 N/A BD 3 0/1 0/1 Spare N N
8 SPARE_BV3 BV3 1541 01,03,05,06,15 N/A BD 3 0/1 0/1 Spare N N
9 LCHLT AI1 514 03,04 x10 ADF 5 °F °C Leaving Chilled Liquid SSerutarepmeT
10 ECHLT AI2 515 03,04 x10 ADF 6 °F °C Entering Chilled Liqu SSerutarepmeT di
11 EV_ELT AI3 516 03,04 x10 ADF 7 °F °C Evaporator Entering Liquid Temperature (Free Cooling) O O
12 VSD_IA_TEMP AI4 517 03,04 x10 ADF 8 °F °C VSD Internal Am SSerutarepmeT tneib
13 S1_C
OND_TEMP AI5 518 03,04 x10 ADF 9 °F °C Sys 1 Condense SSerutarepmeT r
14 S2_COND_TEMP AI6 519 03,04 x10 ADF 10 °F °C Sys 2 Condens SSerutarepmeT re
15 S1_DSCH_TEMP AI7 520 03,04 x10 ADF 11 °F °C Sys 1 Dischar SSerutarepmeT eg
16 S2_DSCH_TEMP AI8 521 03,04 x10 ADF 12 °F °C Sys 2 Dischar SSerutarepmeT eg
17 OAT AI9 522 03,04 x10 ADF 13 °F °C Ambient Air Temperatur SSe
18 S1_EDT_TEMP AI10 523 03,04 x10 ADF 14 °F °C Sys 1 Eductor OSerutarepmeT
19 S2_EDT_TEMP AI11 524 03,04 x10 ADF 15 °F °C Sys 2 Eductor OSerutarepmeT
20 S1_OIL_PRESS AI12 525 03,04 x10 ADF 16 PSI BAR Sys 1 Oil Pressure S S
21 S2_OIL_PRESS AI13 526 03,04 x10 ADF 17 PSI BAR Sys 2 Oil Pressure S S
22 S1_SUCT_PRES AI14 527 03,04 x10 ADF 18 PSI BAR Sys 1 Suction Pressure S S
23 S2_SUCT_PRES AI15 528 03,04 x10 ADF 19 PSI BAR Sys 2 Suction Pressure S S
24 S1_DSCH_PRES AI16 529 03,04 x10 ADF 20 PSI BAR Sys 1 Disc SSerusserP egrah
25 S2_DSCH_PRES AI17 530 03,04 x10 ADF 21 PSI BAR Sys 2 Disc SSerusserP egrah
26 S1_MC_FLA AI18 531 03,04 x10 ADF 22 % % Sys 1 Motor Current FLA S S
27 S2_MC_F
LA AI19 532 03,04 x10 ADF 23 % % Sys 2 Motor Current FLA S S
28 S1_OP_HRS AI20 533 03,04 x1 ADF 24 None None Sys 1 Operating Hours S S
29 S2_OP_HRS AI21 534 03,04 x1 ADF 25 None None Sys 2 Operating Hours S S
30 S1_COMP_ST AI22 535 03,04 x1 ADF 26 None None Sys 1 Compr SSstratS rosse
31 S2_COMP_ST AI23 536 03,04 x1 ADF 27 None None Sys 2 Compr SSstratS rosse
32 S1_HI_MTR_T AI24 537 03,04 x10 ADF 28 °F °C Sys 1 Highest SSerutarepmeT rotoM
ANALOG WRITE POINTS
BINARY WRITE POINTS
031-03476-010
031-03476-010
YVAA YVFA YAGK
Board: 031-03478Modbus RTU, BACnet MS/TP, N2 Data Map
Comments
Y.ACS.20.02
Y.ACS.20.04, Y.ACS.20.05
N2 Metasys
Engineering Units Point List Code: S = Standard O = Optional N = Not Available
Version York P/N
Item
Ref
Num
BACnet Name
BACnet
Object
Instance
Modbus
Address
Modbus Data Type
Supported
Modbus
Scaling
(See
Note 5)
New
Updated
YVAA YVFA YAGK Native 3 OCT 17
Property of Johnson Controls, Inc.
Subject to change without notice.
1 of 4
TABLE 13 - YVAA NATIVE COMMUNICATIONS DATA MAP

Table of Contents

Other manuals for York YVAA

Related product manuals