JOHNSON CONTROLS
116
SECTION 7 - OPERATION
FORM 201.28-NM1.1
ISSUE DATE: 1/31/2018
2/16/2016
ENG
POINT LIST CODE: S = STANDARD O = OPTIONAL N = NOT AVAILABLE PAGE
Address Scale Imper SI
POINT LIST DESCRIPTION
1
2
3
4
5
6
7
8
9
10
REF
P43
BV12
YT2_ S01_ P43 nvoYTS01p043 SNVT_switch (95) BD 12 0072 N
/A 0 / 1 0 / 1 Sys 2 VI Step Solenoid Valve 1 Status S S SSS P43
P44
BV13
YT2_ S01_ P44 nvoYTS01p044 SNVT_switch (95) BD 13 0073 N
/A 0 / 1 0 / 1 Sys 1 VI Step Solenoid Valve 2 Status S S SSS P44
P45
BV14
YT2_ S01_ P45 nvoYTS01p045 SNVT_switch (95) BD 14 0074 N
/A 0 / 1 0 / 1 Sys 2 VI Step Solenoid Valve 2 Status S S SSS P45
P46
BV15
YT2_ S01_ P46 nvoYTS01p046 SNVT_switch (95) BD 15 0075 N
/A P46
P47
BV16
YT2_ S01_ P47 nvoYTS01p047 SNVT_switch (95) BD 16 0076 N
/A P47
P48
BV17
YT2_ S01_ P48 nvoYTS01p048 SNVT_switch (95) BD 17 0077 N
/A P48
P49
BV18
YT2_ S01_ P49 nvoYTS01p049 SNVT_switch (95) BD 18 0078 N
/A P49
P50
BV19
YT2_ S01_ P50 nvoYTS01p050 SNVT_switch (95) BD 19 0079 N
/A 0 / 1 0 / 1 S1-1 Cooling Type: 0=Water, 1=Glycol S SSSS P50
P51
BV20
YT2_ S01_ P51 nvoYTS01p051 SNVT_switch (95) BD 20 0080 N
/A 0 / 1 0 / 1 Local/Remote Control Mode: 0 = Local, 1 = Remote SSSSS P51
P52
BV21
YT2_ S01_ P52 nvoYTS01p052 SNVT_switch (95) BD 21 0081 N
/A 0 / 1 0 / 1 Display Units Mode: 0 = Imperial, 1 = SI SSSSS P52
P53
BV22
YT2_ S01_ P53 nvoYTS01p053 SNVT_switch (95) BD 22 0082 N
/A P53
P54
BV23
YT2_ S01_ P54 nvoYTS01p054 SNVT_switch (95) BD 23 0083 N
/A P54
P55
BV24
YT2_ S01_ P55 nvoYTS01p055 SNVT_switch (95) BD 24 0084 N
/A P55
P56
MV1
YT2_ S01_ P56 nvoYTS01p056 SNVT_count_f (51) ADI 1 0030
X 1 enum enum *Sys 1 Operational Code SSSSS P56
P57
MV2
YT2_ S01_ P57 nvoYTS01p057 SNVT_count_f (51) ADI 2 0031
X 1 enum enum *Sys 1 Fault Code SSSSS P57
P58
MV3
YT2_ S01_ P58 nvoYTS01p058 SNVT_count_f (51) ADI 3 0032
X 1 enum enum *Sys 2 Operational Code SSSSS P58
P59
MV4
YT2_ S01_ P59 nvoYTS01p059 SNVT_count_f (51) ADI 4 0033
X 1 enum enum *Sys 2 Fault Code SSSSS P59
P60
MV5
YT2_ S01_ P60 nvoYTS01p060 SNVT_count_f (51) ADI 5 0034
X 1 count count Sys 1 Condenser Fan Stage (0-14) SSSSS P60
P61
MV6
YT2_ S01_ P61 nvoYTS01p061 SNVT_count_f (51) ADI 6 0035
X 1 count count Sys 1 Condenser Fan Speed (vsd) SSSSS P61
P62
MV7
YT2_ S01_ P62 nvoYTS01p062 SNVT_count_f (51) ADI 7 0036
X 1 count count Sys 2 Condenser Fan Stage (0-14) SSSSS P62
P63
MV8
YT2_ S01_ P63 nvoYTS01p063 SNVT_count_f (51) ADI 8 0037
X 1 count count Sys 2 Condenser Fan Speed (vsd) SSSSS P63
P64
MV9
YT2_ S01_ P64 nvoYTS01p064 SNVT_count_f (51) ADI 9 0038
X 1 count count Lead System Number SSSSS P64
P65
MV10
YT2_ S01_ P65 nvoYTS01p065 SNVT_count_f (51) ADI 10 003
9 X 1 enum enum Spare P65
P66
AV30
YT2_ S01_ P66 nvoYTS01p066 SNVT_count_f (51) ADF 30 0040 X 1 °F °C Local Leaving Chilled Liquid Setpoint S S S S S P
66
P67
AV31
YT2_ S01_ P67 nvoYTS01p067 SNVT_count_f (51) ADF 31 0041 X 1 °F °C Low Leaving Chilled Liquid Temp Cutout S S S S S
P67
P68
AV32
YT2_ S01_ P68 nvoYTS01p068 SNVT_count_f (51) ADF 32 004
2 X 1 % % Sys 1 Economizer Valve % Open SSSSS P68
P69
AV33
YT2_ S01_ P69 nvoYTS01p069 SNVT_count_f (51) ADF 33 004
3 X 1 % % Sys 2 Economizer Valve % Open SSSSS P69
P70
AV34
YT2_ S01_ P70 nvoYTS01p070 SNVT_count_f (51) ADF 34 004
4 X 10 PSI BAR Low Suction Pressure Cutout SSSSS P70
P71
AV35
YT2_ S01_ P71 nvoYTS01p071 SNVT_count_f (51) ADF 35 004
5
X1 *
volts volts VSD DC Bus Voltage SSSSS P71
P72
AV36
YT2_ S01_ P72 nvoYTS01p072 SNVT_count_f (51) ADF 36 004
6
X1 *
°F °C Remote Leaving Chilled Liquid Setpoint S S S S S P72
P73
AV37
YT2_ S01_ P73 nvoYTS01p073 SNVT_count_f (51) ADF 37 004
7 X1 * °F °C Sys 1 Subcooling SSSSS P73
P74
AV38
YT2_ S01_ P74 nvoYTS01p074 SNVT_count_f (51) ADF 38 004
8 X1 * °F °C Cooling Range SSSSS P74
P75
AV39
YT2_ S01_ P75 nvoYTS01p075 SNVT_count_f (51) ADF 39 004
9
X1 *
°F °C Sys 1 Discharge Superheat SSSSS P75
P76
AV40
YT2_ S01_ P76 nvoYTS01p076 SNVT_count_f (51) ADF 40 005
0 X 1 °F °C Sys 2 Condenser Temperature SSSSS P76
P77
AV41
YT2_ S01_ P77 nvoYTS01p077 SNVT_count_f (51) ADF 41 005
1 X 1 °F °C Sys 2 Discharge Temperature SSSSS P77
P78
AV42
YT2_ S01_ P78 nvoYTS01p078 SNVT_count_f (51) ADF 42 005
2 X 1 °F °C Sys 2 Subcooling SSSSS P78
P79
AV 43
YT2_ S01_ P79 nvoYTS01p079 SNVT_count_f (51) ADF 43 005
3 X 1 °F °C Sys 2 Discharge Superheat SSSSS P79
P80
BV25
YT2_ S01_ P80 nvoYTS01p080 SNVT_switch (95) BD 25 0085 N
/A 0/1 0/1 Sys 1 Lockout SSSSS P80
P81
BV26
YT2_ S01_ P81 nvoYTS01p081 SNVT_switch (95) BD 26 0086 N
/A 0/1 0/1 Sys 2 Lockout SSSSS P81
P82
BV27
YT2_ S01_ P82 nvoYTS01p082 SNVT_switch (95) BD 27 0087 N
/A P82
P83
BV28
YT2_ S01_ P83 nvoYTS01p083 SNVT_switch (95) BD 28 0088 N
/A P83
P84
BV29
YT2_ S01_ P84 nvoYTS01p084 SNVT_switch (95) BD 29 0089 N
/A P84
2
4
5
6
7
8
9
10
NOTE: The Appropriate Product Code Listing Summary Should Accompany Document
see note 3
Codes
are available only in Firmware versions C.A21.14.0
3 or later. Contact your JCI FSC for assistance on upgrading your firmware
3
MODBUS scaling factors indicated in BOLD with an (*
) asterisk are User Configurable, by a field technician if necessary. All Modbus values are of the type SIGNED with the exception of the User Configurabale values that are all
UNSIGNED. Modbus Function Types Supported
(ENG P03-P06 = Types 03, 06, 16) , ( ENG P07- P10 = 01, 03, 05, 15, 06, 16), (ENG P11-P35, P56-P79) = 03, 04) , (ENG P36-P55, P80 -P84 = 01, 02, 03)
ENG UNITS
LON SNVT Type
N2
Metasys
MODBUS
BACnet
Object
Typ/Ins
Bacnet Object
Name
LON Profile
Name
1
LON SNVTS Used: SNVT_count (8), SNVT_lev_percent (81), SNVT_te
mp_p (105), SNVT_switch (95) , SNVT_time_minute (123) , SNVT_freq_hz (76) , SNVT_amp (01) , SNVT_elec_kwh (13) , SNVT_power_kilo (83) ,
SNVT_volt (44) , SNVT_volt_ac (138), SNVT_press_p
(87)
NOTES
ENG
PAGE
Ref
BACnet Engineering Units shown with an (*) Asterisk will be assigned a BACn
et Eng Unit type of (95) ie NO UNITS.
Status Codes: Special Display characters such as (, ), [, ],
{, },/,\,%,< and > are not compatible with Elink N2 formats. Substitute text strings , "-", PCT, GTN will be used .
Status Codes: Status Code Text string lengths are limited to 60
total characters (including spaces)
Revision: YVAA_YVFA BAS (Rev K_03h).xlsx Tab: YV
AA_YVFA Property of Johnson Controls, York, PA Page: 2
TABLE 15 - YVAA E-LINK COMMUNICATIONS DATA MAP (CONT'D)