JOHNSON CONTROLS
152
SECTION 8 - MICROPANEL
FORM 201.28-NM1.1
ISSUE DATE: 1/31/2018
OPTIONS REMOTE CURRENT LIMIT INPUT
â—„ â–º 0.0 TO 10.0 VOLTS DC
OPTIONS REMOTE CURRENT LIMIT INPUT
â—„ â–º 2.0 TO 10 VOLTS DC
OPTIONS REMOTE CURRENT LIMIT INPUT
â—„ â–º 0.0 TO 20.0 MILLIAMPS
OPTIONS REMOTE CURRENT LIMIT INPUT
â—„ â–º 4.0 TO 20.0 MILLIAMPS
The default setting for Remote Current Reset is
DISABLED. This display will only appear if the re-
mote current limit option is enabled under the Unit
Setup Mode.
Remote Sound Limit Selection
Remote sound limit from an external source may be
tied directly into the chiller microprocessor board.
OPTIONS REMOTE SOUND LIMIT INPUT
â—„ â–º XXXXXXXXXXXXXXXXXXXX
Selections may be made for DISABLED (no signal),
0 to 10VDC, 2 to 10VDC, 0 to 20ma, and 4 to 20ma.
OPTIONS REMOTE SOUND LIMIT INPUT
â—„ â–º DISABLED
OPTIONS REMOTE SOUND LIMIT INPUT
â—„ â–º 0.0 TO 10.0 VOLTS DC
OPTIONS REMOTE SOUND LIMIT INPUT
â—„ â–º 2.0 TO 10.0 VOLTS DC
OPTIONS REMOTE SOUND LIMIT INPUT
â—„ â–º 0.0 TO 20.0 MILLIAMPS
OPTIONS REMOTE SOUND LIMIT INPUT
â—„ â–º 4.0 TO 20.0 MILLIAMPS
The default setting for Remote Sound Limit is
DISABLED. This display will only appear if the re-
mote sound limit option is enabled under the Unit Set-
up Mode.
Low Ambient Cutout Enable/Disable
The low ambient cutout may be enabled or disabled.
When enabled, the chiller will cut OFF when the low
ambient cutout is reached. When disabled, the chiller
will run at any temperature.
OPTIONS LOW AMBIENT TEMPERATURE CUTOUT
â—„ â–º ENABLED
OPTIONS LOW AMBIENT TEMPERATURE CUTOUT
â—„ â–º DISABLED
The default setting for the low ambient cutout will be
ENABLED.