EasyManua.ls Logo

York YVAA - Installation; Location Requirements; Location Clearances

York YVAA
178 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SECTION 3 - RIGGING, HANDLING AND STORAGE
JOHNSON CONTROLS
29
FORM 201.28-NM1.1
ISSUE DATE: 1/31/2018
3
LD18582
TABLE 1 - UNIT RIGGING (CONT'D)
YVAA MODEL
DESCRIPTION UNITS
RIGGING HOLES
FRAME COND EVAP I J K L M N O P
015 3 B
Rigging Hole
Location
inches 18 60 116 192
mm 464 1511 2937 4866
016 5 B
Rigging Hole
Location
inches 18 60 137 214
mm 464 1533 3485 5435
017 8 C
Rigging Hole
Location
inches 12 73 144 197 260
mm 314 1845 3654 5012 6593
018 3 A
Rigging Hole
Location
inches 18 60 143 220
mm 464 1533 3636 5598
019 5 A
Rigging Hole
Location
inches 18 60 143 227 272
mm 464 1533 3636 5761 6920
019 8 B
Rigging Hole
Location
inches 18 60 137 215 302
mm 464 1533 3484 5455 7670
020 0 C
Rigging Hole
Location
inches 60 131 214
mm 1518 3332 5430
021 3 A
Rigging Hole
Location
inches 18 60 143 227 272
mm 464 1533 3637 5761 6920
021 5 C
Rigging Hole
Location
inches 12 73 144 197 260
mm 314 1845 3654 5012 6593
021 8 C
Rigging Hole
Location
inches 12 73 163 254 324
mm 314 1845 4144 6443 8218
NOTE: Rigging and lifting the unit must be done safely by a professional rigger as discussed in this section. The rigger should locate the center of
gravity through trial lifts to account for possible variations in unit conguration. Contact your nearest Johnson Controls Sales Ofce for weight data.

Table of Contents