SECTION 3 - RIGGING, HANDLING AND STORAGE
JOHNSON CONTROLS
33
FORM 201.28-NM1.1
ISSUE DATE: 1/31/2018
3
LD18582
TABLE 1 - UNIT RIGGING (CONT'D)
YVAA MODEL
DESCRIPTION UNITS
RIGGING HOLES
FRAME COND EVAP I J K L M N O P
030 5 C
Rigging Hole
Location
inches 12 73 161 254 306 391
mm 314 1845 4092 6443 7763 9941
030 8 E
Rigging Hole
Location
inches 12 73 121 179 243 296 391
mm 314 1845 3072 4549 6169 7508 9942
031 8 E
Rigging Hole
Location
inches 12 73 121 179 243 353 435
mm 314 1845 3072 4549 6169 8962 11059
032 3 E
Rigging Hole
Location
inches 12 73 121 181 243 347
mm 314 1845 3073 4601 6169 347
033 3 C
Rigging Hole
Location
inches 12 73 163 254 306 391
mm 314 1845 4144 6443 7765 9942
034 3 E
Rigging Hole
Location
inches 12 73 121 181 243 296 391
mm 314 1845 3073 4602 6170 7511 9942
034 5 E
Rigging Hole
Location
inches 12 73 121 181 243 353 435
mm 314 1845 3073 4602 6170 8961 11059
036 8 J
Rigging Hole
Location
inches 12 73 181 238 302 392 434 501
mm 314 1845 4602 6039 7662 9957 11024 12725
037 3 F
Rigging Hole
Location
inches 12 73 181 238 302 435
mm 314 1845 4602 6039 7662 11059
037 5 J
Rigging Hole
Location
inches 12 73 181 238 302 435
mm 314 1845 4602 6039 7662 11059
NOTE: Rigging and lifting the unit must be done safely by a professional rigger as discussed in this section. The rigger should locate the center of
gravity through trial lifts to account for possible variations in unit conguration. Contact your nearest Johnson Controls Sales Ofce for weight data.