EasyManua.ls Logo

York YVAA - Page 61

York YVAA
178 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SECTION 4 - INSTALLATION
JOHNSON CONTROLS
61
FORM 201.28-NM1.1
ISSUE DATE: 1/31/2018
4
TABLE 4 - ELECTRICAL LUG DATA (CONT'D)
FIELD WIRING LUGS TERMINAL BLOCK
TERMINAL BLOCK
WITH INDEPENDENT
SYSTEM CIRCUIT
BREAKERS
TERMINAL BLOCK WITH
INDEPENDENT SYSTEM
NON-FUSED DISCONNECT
SWITCHES
SINGLE POINT WIRING
YVAA MODEL
INPUT
VOLTS
INPUT
FREQ
WIRES
PER
PHASE
LUG WIRE
RANGE
WIRES
PER
PHASE
LUG WIRE
RANGE
WIRES PER
PHASE
LUG WIRE
RANGE
FRAME
COND
EVAP
Models
0368 to 0523
200 60
230 60
380 60 4 #1 - 750 kcmil 4 #1 - 750 kcmil 4 #1 - 750 kcmil
400 50 4 #1 - 750 kcmil 4 #1 - 750 kcmil 4 #1 - 750 kcmil
460 60 4 #1 - 750 kcmil 4 #1 - 750 kcmil 4 #1 - 750 kcmil
575 60 4 #1 - 750 kcmil 4 #1 - 750 kcmil 4 #1 - 750 kcmil
FIELD WIRING LUGS
HIGH AIRFLOW/HIGH STATIC CONDENSER FANS
TERMINAL
BLOCK
CIRCUIT
BREAKER
NON-FUSED
DISCONNECT SWITCH
YVAA MODEL
INPUT
VOLTS
INPUT
FREQ
WIRE
PER
PHASE
LUG
WIRE
RANGE
WIRES
PER
PHASE
LUG
WIRE
RANGE
WIRES
PER
PHASE
LUG
WIRE
RANGE
FRAME COND EVAP
DUAL POINT WIRING
048 3 G
200 60
230 60
380 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil
400 50 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil
460 60 2 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil
575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #1 ~ 500 kcmil
49 0 K
200 60
230 60
380 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil
400 50 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil
460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #3/0 ~ 400 kcmil
575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #1 ~ 500 kcmil
050 0 J
200 60
230 60
380 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil
400 50 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil
460 60 2 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil
575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #1 ~ 500 kcmil
052 3 J
200 60
230 60
380 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil
400 50 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil
460 60 2 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil
575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #1 ~ 500 kcmil