5167821-YTG-K-1118
106 Johnson Controls Ducted Systems
150
(12.5)
208 17.6 17.6 136 136 27 27 3.5 9.6 5.5
None - - - 63.2 68.7 80 80
E18 13.5 2 37.5 63.2 68.7 80 80
E24 18 2 50 74.5 81.4 80 90
E36 25.5 2 70.8 100.5 107.4 110 110
E54 40.6 2 112.7 152.9 159.8 175 175
230 17.6 17.6 136 136 27 27 3.5 9.6 5.5
None - - - 63.2 68.7 80 80
E18 18 2 43.3 66.1 73 80 80
E24 24 2 57.7 84.1 91 90 100
E36 34 2 81.8 114.3 121.1 125 125
E54 54 2 129.9 141.9 148.8 175 175
460 8.5 8.5 66.1 66.1 13 13 1.6 4.7 2.2
None - - - 30.2 32.4 35 40
E18 18 2 21.7 33 35.8 35 40
E24 24 2 28.9 42 44.8 45 45
E36 34 2 40.9 57 59.8 60 60
E54 54 2 65 70.9 73.6 80 80
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
ZT037-150 standard indoor blower - without powered convenience outlet (continued)
Size
(tons)
Volt
Compressors
(each)
OD fan
motors
(each)
Supply
blower
motor
Pwr
exh
motor
Pwr
conv
outlet
Electric heat option
MCA
1
(amps)
MCA
1
with pwr
exh
(amps)
Max fuse
2
/
breaker
3
size
(amps)
Max fuse
2
/
breaker
3
size with
pwr exh
(amps)
RLA LRA MCC
C1 C2 C1 C2 C1 C2 FLA FLA FLA FLA Model kW Stages Amps