5167821-YTG-K-1118
112 Johnson Controls Ducted Systems
150
(12.5)
208 17.6 17.6 136 136 27 27 3.5 9.6 5.5 20
None - - - 73.2 78.7 90 90
E18 13.5 2 37.5 73.2 78.7 90 90
E24 18 2 50 87 93.9 90 100
E36 25.5 2 70.8 113 119.9 125 125
E54 40.6 2 112.7 165.4 172.3 175 175
230 17.6 17.6 136 136 27 27 3.5 9.6 5.5 20
None - - - 73.2 78.7 90 90
E18 18 2 43.3 78.6 85.5 90 90
E24 24 2 57.7 96.6 103.5 100 110
E36 34 2 81.8 126.8 133.6 150 150
E54 54 2 129.9 154.4 161.3 175 175
460 8.5 8.5 66.1 66.1 13 13 1.6 4.7 2.2 20
None - - - 35.2 37.4 40 45
E18 18 2 21.7 39.3 42 40 45
E24 24 2 28.9 48.3 51 50 60
E36 34 2 40.9 63.3 66 70 70
E54 54 2 65 77.1 79.9 90 90
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
ZT037-150 standard indoor blower - with powered convenience outlet (continued)
Size
(tons)
Volt
Compressors
(each)
OD fan
motors
(each)
Supply
blower
motor
Pwr
exh
motor
Pwr
conv
outlet
Electric heat option
MCA
1
(amps)
MCA
1
with pwr
exh
(amps)
Max
fuse
2
/
breaker
3
size
(amps)
Max fuse
2
/
breaker
3
size with
pwr exh
(amps)
RLA LRA MCC
C1 C2 C1 C2 C1 C2 FLA FLA FLA FLA Model kW Stages Amps