5167821-YTG-K-1118
Johnson Controls Ducted Systems 35
115°F 125°F
750
77 29.3 2.2 12.1 6.8 5.8 - - - 27.3 2.5 11.2 5.5 4.6 - - -
72 24.3 2.2 15.7 12.7 9.6 6.6 - - 22.0 2.5 13.9 11.1 8.2 5.4 - -
67 19.3 2.3 19.3 18.5 13.5 10.5 7.5 - 16.7 2.6 16.7 16.7 11.8 8.9 6.1 -
62 17.1 2.3 17.1 17.1 12.7 9.7 6.6 3.6 15.3 2.5 15.3 15.3 11.0 8.2 5.3 2.5
900
77 29.3 2.2 16.8 10.1 6.4 - - - 27.1 2.5 15.7 8.8 5.2 - - -
72 24.3 2.2 18.1 14.4 10.7 7.1 - - 21.8 2.5 16.1 12.7 9.2 5.7 - -
67 19.3 2.3 19.3 18.7 15.1 11.4 7.7 - 16.5 2.6 16.5 16.5 13.2 9.7 6.2 -
62 17.1 2.3 17.1 17.1 14.2 10.5 6.8 3.2 15.2 2.5 15.2 15.2 12.3 8.9 5.4 1.9
57 16.4 2.3 16.4 16.4 13.5 9.9 6.2 2.5 13.1 2.5 13.1 13.1 10.6 7.1 3.6 0.2
1050
77 29.3 2.2 21.6 13.3 7.1 - - - 26.9 2.5 20.3 12.1 5.7 - - -
72 24.3 2.2 20.5 16.2 11.9 7.6 - - 21.7 2.5 18.4 14.3 10.2 6.1 - -
67 19.3 2.3 19.3 19.0 16.6 12.3 8.0 - 16.4 2.6 16.4 16.4 14.6 10.5 6.4 -
62 17.1 2.3 17.1 17.1 15.6 11.3 7.0 2.7 15.1 2.6 15.1 15.1 13.6 9.5 5.4 1.3
57 16.4 2.3 16.4 16.4 14.9 10.6 6.3 2.0 13.0 2.6 13.0 13.0 11.7 7.6 3.5 -0.6
1200
77 29.3 2.2 26.4 16.6 7.8 - - - 26.7 2.5 24.9 15.5 6.3 - - -
72 24.3 2.2 22.9 17.9 13.0 8.1 - - 21.5 2.5 20.6 15.9 11.1 6.4 - -
67 19.3 2.3 19.3 19.3 18.2 13.3 8.3 - 16.3 2.6 16.3 16.3 16.0 11.3 6.5 -
62 17.1 2.3 17.1 17.1 17.1 12.2 7.2 2.3 14.9 2.6 14.9 14.9 14.9 10.2 5.5 0.8
57 16.4 2.3 16.4 16.4 16.4 11.4 6.5 1.5 12.9 2.6 12.9 12.9 12.9 8.1 3.4 -1.3
1350
72 24.7 2.2 24.0 19.2 13.6 8.0 - - 22.0 2.5 21.5 16.9 11.5 6.1 - -
67 19.6 2.3 19.6 19.6 19.1 13.5 7.9 - 16.7 2.6 16.7 16.7 16.5 11.1 5.8 -
62 17.4 2.3 17.4 17.4 17.4 11.8 6.2 0.6 15.3 2.6 15.3 15.3 15.3 9.9 4.6 -0.8
57 16.7 2.3 16.7 16.7 16.7 11.1 5.5 -0.1 13.2 2.6 13.2 13.2 13.2 7.8 2.4 -2.9
1500
72 25.2 2.2 25.2 20.5 14.3 8.0 - - 22.5 2.5 22.5 17.9 11.9 5.8 - -
67 20.0 2.3 20.0 20.0 20.0 13.7 7.5 - 17.0 2.6 17.0 17.0 17.0 11.0 5.0 -
62 17.7 2.3 17.7 17.7 17.7 11.5 5.2 -1.0 15.6 2.6 15.6 15.6 15.6 9.6 3.6 -2.4
57 17.0 2.3 17.0 17.0 17.0 10.7 4.4 -1.8 13.5 2.6 13.5 13.5 13.5 7.5 1.5 -4.5
1. These capacities are gross ratings. For net capacity, deduct the air blower motor, MBh = 3.415 x kW. Refer to the appropriate blower
performance table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZT078 (6.5 ton) 1st stage cooling (continued)
Air on evaporator
coil
Temperature of air on condenser coil
Total
capacity
1
(MBh)
Total input
(kW)
2
Sensible capacity (MBh)
Total
capacity
1
(MBh)
Total input
(kW)
2
Sensible capacity (MBh)
CFM
WB
(°F)
Return dry bulb (°F) Return dry bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65