Response time : ≤0.5s ( when digital filter parameter FILt=0)
Alarm function : High limit, low limit, deviation high limit and deviation low limit; providing the function of alarm
blocking at the beginning of power on.
Control period : 0.24~300.0 seconds selectable, and it should be integer times of 0.5 second.
Control mode:
On-off control mode (dead band adjustable)
Standard PID with auto tuning
AI PID with auto tuning, adopting artificial intelligence algorithm.
Output mode (modularized)
Relay output (NO+NC): 250VAC/2A, 30VDC/2A, 250VAC/1A and 30VDC/1A
TRIAC no contact discrete output (NO or NC): 100~240VAC/0.2A (continuous), 2A (20mS instantaneous,
repeat period≥5s)
SSR Voltage output: 12VDC/30mA (used to drive SSR).
Thyristor zero crossing trigger output: Can trigger TRIAC of 5~500A, a pair of inverse paralleled SCRs or
SCR power module.
Linear current output: 0~20mA, 4 ~2 0 m A can scaling by user. (Output voltage : X3 ≥10.5V; X5 ≥7V
maximum load resistor 500ohm, output precision 0.2%FS)
Electromagnetic compatibility (EMC): ±4KV/5KHz according to IEC61000-4-4; 4KV according to
IEC61000-4-5.