4. Further description for the operation of AI-526P series instrument
AI-526P v8.0 program type temperature controller is used in the application where the setpoint should be changed
automatically with the time. It provides 30 segments program control which can be set in any slope and the function of
jump, run, hold and stop can also be set in the program. Measurement startup function, preparation function and
power-cut/power-resume event handling modes also provided.
4.1 Concepts and functions Program
StEP:
The No. of the program S t e p can be defined from 1 to 30, and the current S t e p is the program S t e p being executing.
S t E P t i m e :
Total run time of the program step. The unit is minute and the available value range from 1 to 9999.
Running time:
The Time of current S t e p has run. As the running time reaches the S t e p time, the program will jump to the next S t e p
automatically.